background image

 

1

MACURCO GAS DETECTORS 

ND-1 

INSTALLATION & OPERATING INSTRUCTIONS 

WWW.MACURCO.COM

 

 

GENERAL INFORMATION 

 The ND-1 is a microcomputer controlled electronic sensor and controller for Nitrogen Dioxide (NO

2

).  The 

unit has a NO

2

 sensor (electrochemical), digital display, status lights, buzzer and relays.  Please see the ND-1 data 

sheet for more detailed information. 
 

LOCATION 

 The unit, on average, can cover about 5000 sq. ft. (465 sq. meters).  The coverage depends on air movement in 
the room or facility.  Extra detectors may be needed near any areas where people work, or the air is stagnant.  
Normally, the unit mounts 5 feet (1.5 meters) above the floor in a central area where air movement is generally 
good.  See the ND-1 data sheet for more information on location. 
 

INSTALLATION 

 The

 

ND-1 is housed in an electrical box that has mounting holes on the back.  Conduit can be connected to the 

bottom three knock-out holes.  Do NOT remove the four black vents in the case.  They are necessary for adequate 
air flow into the unit.  Remove the two small screws toward the 

bottom

 of the inside cover.  The inside cover then 

swings up for access to internal circuitry. 
 Once the cover is open, you should notice a seven-screw terminal block.  The first two screws, at the far left, 
are for power and are marked “POWER 12-24 V ac/dc”.  There is no polarity.  The three middle terminals are for 
the Fan SPDT relay.  They are marked from left to right N.O. (normally-open), COM (common), and N.C. 
(normally-closed).  The Fan relay contacts can handle up to 5 amps.  The two terminals at the far right are for the 
Alarm relay.  They are both marked N.O. (normally-open).  The Alarm relay contacts can handle up to 0.5 amps. 
 The relays have dry contacts.  See the ND-1 data sheet for detailed schematics on wiring and other technical 
information. 
 

OPERATION 

 When power is first applied to the detector, it will go through a warm-up period of 30 seconds.  The digital 
display will count down from 30 to 0 during the warm-up period.  The Fan and Alarm relays will also actuate 
during the warm-up period. 
 The ND-1 is now operational.  Set the Fan and Alarm PPM levels as needed for the job requirements.  The 

current OSHA and ACGIH values for 

NO

2

 are TWA of 3 ppm (parts per million) and STEL of 5 ppm.  The 

suggested settings to meet those limits are a Fan setting of 3 ppm and an Alarm setting of 5 ppm. 
 The Fan turn-on delay can be set from 0 to 5 minutes by setting the 3-segment “FAN DELAY” switch (inside 
the unit just below the big blue buzzer).  When the turn-on delay has been actuated by the NO

2

 level exceeding the 

threshold settings, the amber light will flash.  When the turn-on delay is over the amber light will come on solid 
and the Fan relay will actuate. 

 

FAN DELAY SWITCH CHART 

 
 
 
    NONE   30 SEC.  45 SEC. 1 MIN.      2 MIN.     3 MIN.   4 MIN.   5 MIN. 

 

The Alarm turn-on delay (flashing red) is fixed at 5 minutes.  A solid red light indicates Alarm relay 

activation, and the buzzer will sound. Both Fan and Alarm relays have a minimum on-time of 30 seconds.  This is 
to prevent short cycling devices connected to the relays. 
 

TESTING 

 Testing the unit can be done by pressing the “TEST” switch located near the buzzer on the printed circuit 
board.  This will initiate the test cycle.  The display will read 88.8, both the Fan and Alarm relays will actuate, 
both Fan and Alarm status lights will be on solid, and the buzzer will sound.  The test cycle will last approximately 
30 seconds. 

Reviews: