Aerosol CO Field Test Gas CME1-FTG
User Instructions
IMPORTANT: Keep these User Instructions for reference.
Page 1: ...1 Macurco Aerosol CO Field Test Gas CME1 FTG User Instructions IMPORTANT Keep these User Instructions for reference ...
Page 2: ...ot do not proceed with tests See CM 6 Trouble Indicator section 1 The display option should be set to On and reading 0 ppm in clean air 2 With the cover in place direct the gas into the housing by placing the nozzle of the aerosol can onto the sensor grate area under DO NOT PAINT and press for 2 to 3 seconds 3 Wait for a few seconds The digital display should climb indicating the increased CO conc...
Page 3: ...o 0 ppm and configure options to desired settings Testing the Alarm Relay Note The CO concentration to activate the Alarm relay depends on the setting 1 With the display function turned On the CM 6 will show the current concentration of CO or 0 zero in clean air 2 With the cover in place direct the gas into the housing by placing the nozzle of the aerosol can onto the sensor grate area under DO NO...
Page 4: ...curco warrants the CME1 FTG field test gas will be free from defective materials and workmanship for a period of two 1 years from date of manufacture indicated on the gas bottle label provided it is maintained and used in accordance with Macurco instructions and or recommendations If any component becomes defective during the warranty period it will be replaced or repaired free of charge if the un...