l
Registers are inverse float values
l
Float values are formatted according to IEEE 744 32-bit representation
l
Register size is 32-bit
l
Flow total has a range from 0 to 999999.9
System registers:
The XCi device includes system registers that contain the following information:
Register pair
System information
Type
30101-30102
MACE Serial Number
(unsigned long integer)
30103-30104
System battery (Volts)
(4 byte big-endian IEEE 754 float value)
30105-30106
External voltage (Volts)
(4 byte big-endian IEEE 754 float value)
Configuring a FloSI card in
1. Ensure at least one channel is configured.
2. From the “
Device settings
” dialogue box. Click the "
FloSI
" button and the “
FloSI settings
” dialogue
box will appear.
3. Click “
Change
” and the “
Select output mode
” dialogue box will appear.
4. From the drop down list select the output mode you wish to use. Click “
Apply
” and the updated “
FloSI
settings
” dialogue box will appear.
MACE XCi User Manual - 92 -