NOTE: There is only a single “
Pulse input
” available per “
Pulse card
”.
Edit a "Flowrate (using pulse)" channel type
Module settings
Continuous measurement mode
If selected, the Pulse card will operate in "
Continuous measurement mode
". In this mode all input pulses
will be counted and the pulsing sensor will be continuously powered.
The “
Averaging time
” allows the user to set a period of time over which the pulses will be counted and
averaged. This average is then used to calculate a rolling average which may help in applications with
unstable flow rate pulsing.
Non-Continuous measurement mode
If the "
Continuous measurement mode
" check box is un-selected, the Pulse card will operate in "
Non-
Continuous measurement mode
". The pulsing sensor will only be powered for the “
Integration time
”
specified. In this mode input pulses will only be counted for the configured “
Integration time
” at each
scheduled “
Measurement interval
”.
12V sensor supply
MACE XCi User Manual - 173 -