M2M MQ03-Alarm Installer Manual Download Page 6

 

Configuring the zones 

The MQ03-Alarm supports up to 8 zones. If you need to change the default self-learning behavior, 
you can configure the zones from the “RControl Alarm” menu, section “Zones”. 
With a double click on the selected zone you can: 

 

Change the name of the zone 

– from section “Zone name” 

 

Enable or Disable the zone 

– from section “Enabled” 

 

Set the type of the zone 

– Instant, Enrty/Exit, Follow, Tamper, Panic, Fire and etc. – from 

the menu “Zone type”. Select “Disabled” if the zone will not be used 

 

If you have configured a zone as a “Keyswitch zone” 

you can choose if the alarm panel 

would be Armed/Disarmed when this zone is activated. 

This can be configured from the 

menu “Keyswitch action” 

 

Configure zone arming type = “Full arm” and “Stay arm” – from menu “Keyswitch arming”. 

 

Choose if the siren will be activated when the zone is violated – from section “Notification 
type” 

 

Can choose if every violation of the zone will be reported during the alarm cycle time. You 
can configure this from section 

“Report All During Alarm Cycle”. 

If this setting is disabled 

only the initial violation will be reported and all following activations will not be reported 
until the alarm cycle time expires. When the alarm cycle time expires, the zone restore 
event will be reported only when the zone is really restored. In addition, even when there 
was a restore during the alarm cycle, this restore will not be reported until the expiration of 
the alarm cycle time or until the partition is disarmed. 

Zone types 

 

Entry/Exit zone

 – The Entry/Exit zones can be violated during the entry/exit time delay 

without causing an alarm event. 
If an Entry/Exit zone is violated while the system is armed, the alarm panel will start 
counting the entry time. If the system is not disarmed during the entry time an alarm event 
is generated. 
NOTE! If the entry/exit time is 0 sec, the Entry/Exit zone works as an Instant zone. 

 

 

Follow zone - 

This zone can be violated during the entry/exit delay time without generating 

an alarm event. If the zone is violated while the panel is armed, the panel immediately 
generates an alarm event (without counting entry time).  It is called “Follow” zone because 
it depends on the Entry/Exit zone. If the Follow zone is violated after an Entry/Exit zone has 
also been violated then the alarm panel will wait until the entry time passes before 
generating an alarm event. 
If the Follow zone was violated before any Entry/Exit zone was violated, then an alarm event 
will be generated immediately. 
NOTE! If the entry/exit time is 0sec, the Follow zone will work as an Instant zone. 

 

Summary of Contents for MQ03-Alarm

Page 1: ...d 1 Kukush Str building M8 Sofia 1309 Bulgaria Web Site www m2mservices com M2M Services Ltd 1 Kukush Str building M8 Sofia 1309 Bulgaria Web Site www m2mservices com M2M Services Ltd MQ03 Alarm Installer Manual V 1 2 ...

Page 2: ...ring detectors 3 SMARTEnroll self learning zones 3 Using the wireless keyfobs 4 Pairing a wireless keyfob 4 Deleting a wireless keyfob 4 Configuring the MQ03 Alarm 5 General settings of MQ03 Alarm 5 General settings of the partition 5 Configuring the zones 6 Zone types 6 ...

Page 3: ... the alarm panel The tamper can be connected to a zone configured as 24h tamper SMARTEnroll self learning zones The MQ03 Alarm panel supports SMARTEnroll feature preconfigured settings and self learning zones which in most cases eliminate the need of initial programming of the alarm panel This simplifies the installation process in the most commonly used scenario when only instant zones with no en...

Page 4: ... 2 seconds and then it will start blinking fast This shows that the keyfob has been paired and the procedure was successful You need to repeat this procedure for each additional wireless keyfob separately NOTE 1 If after pressing the white pairing button the RF transceiver does not receive signal from the wireless keyfob within 30 seconds the pairing procedure will be automatically canceled 2 You ...

Page 5: ... the delay in seconds after which the device will report the mains power outage Configuring the Battery level thresholds In section Battery field Battery low you can set a low voltage threshold under which the alarm panel will send Low Battery event In the filed Battery Critical Low you can set even lower voltage threshold and if the battery voltage goes under this level it will be considered as c...

Page 6: ...n the alarm cycle time expires the zone restore event will be reported only when the zone is really restored In addition even when there was a restore during the alarm cycle this restore will not be reported until the expiration of the alarm cycle time or until the partition is disarmed Zone types Entry Exit zone The Entry Exit zones can be violated during the entry exit time delay without causing...

Page 7: ...t zone is violated In this case the alarm panel sends a ContactID event E 374 Exit Error in Zone N reporting the first of all the violated zones which prevent the panel from arming Follow STAY zone This is a Follow zone that is not monitored when the panel is partially armed STAY Arm Instant STAY zone This is an Instant zone that is not monitored when the panel is partially armed STAY Arm ...

Reviews: