Industrial HMI Touch Panel Hardware Manual
M2I Corporation
11-35, Simin-daero 327beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do 14055, Korea, Tel: +82-70-465-3366, Fax: +82-31-465-3355, www.m2i.co.kr
19 / 22
If the screw is over tightened, it may cause the front deformation, thus resulting the touch sensor
can’t work properly Tighten the screws to a torque of 0.2N.m.
Caution: If the torque of screwing is not 0.4N.m, IP specification will not be secured.
(4) I/O Terminal Cable Finishing
After wiring the I/O cables to the product, tighten the cables with a fixing hole on product side and cable tie.
Chapter 8 Wiring
8.1 Power Wiring
Caution: With a power and ground cables’ wiring, using Pin Terminal is important for maintaining product’s
performance. Without using specified Pin Terminals as below, it can cause electric shocks from abnormal cable
connection. Users and managers should must be well-informed of following instructions.
(1) The Power cable should have the following specification.
Power Cable Specification
0.75~2.5mm
2
(18~12AWG)
F.G Cable Specification
Over 4mm
2
(11AWG)
Conductor Type
Simple or Standard Wire
Bolt tightening force
≥ 0.4 N.m
Conductor Length
Temperature rating of the
field installed conductors
65℃ or under