TR30-G USERS MANUAL EM-8631-G Rev.16
Alarm zone setting (PI)
Configure alarm zone setting corresponding to the input values. A maximum of 5 zones can be set, and dead-
bands can also be set between zones.
(1) Click on the [Alarm zone setting] button in the [PI setting] to display the [PI Alarm zone setting].
PI setting
PI alarm zone setting
Click
(2) Set various parameters by referring to the table below.
Parameter
Description
Partitions
Set the number of partitions to be used. You can select from: Disable / 2 / 3 / 4 / 5.
Name
Set a name which is less than 32 characters for each zone.
Color
Set a color to represent each zone which will be displayed on the Web screen.
Upper limit
:
:
:
Lower limit
Set the upper and lower limit value for these zones as actual values. Set the upper limit value
> lower limit value.
• When the deadband is set
When a deadband is set between zone 1 and zone 2, set the values so that the deadband is
between the upper limit value for zone 1 and the lower limit value for zone 2. Set similarly for
the other zones as well.
• When the deadband is not set
When the deadband is not set between zone 1 and zone 2, set the same value for the upper
limit value of zone 1 and the lower limit value of zone 2. Set similarly for the other zones as
well.
Trigger recording
Set whether or not to record when there is a change in the input value and it enters a certain
zone.
You can select from: Disable / Start / Stop.
New memory block
Set whether or not to run a new memory block when there is a change in the input value and it
enters a certain zone.
You can select from: Disable / Enable.