INSTALLATION

 CAUTION

• IP 55 is ensured for the front panel of the unit mounted 

independently to a panel.  Test the sealing at the mount-
ing surface once the device is installed.

• Set the unit on a vertical surface with its digital meter at 

the top side.  Mounting in other directions may cause heat 
built up inside the unit and shorten its life or degrade its 
performance.

• Ensure that there is sufficient space for ventilation inside 

a panel. Do not install above the devices that generate 
high heat such as heaters, transformers or resistors.  
Observe at the minimum of 30 mm (1.2”) in all directions 
for maintenance purpose (e.g. wiring, removing or install-
ing).

 HOW TO MOUNT THE UNIT ON A PANEL

1)  Remove both mounting brackets.
2)  Detach the terminal cover and insert it first and then the 

module itself into the cutout hole. (The cover is slightly 
wider than the module.)

3)  Put and slide the brackets back into the holes at the top 

and the bottom and tighten them until the module is 
firmly fixed.

 HOW TO REMOVE THE TERMINAL COVER

Insert the minus tip of a screwdriver into each hole at the 
four corners of the cover and pull it to the direction as indi-
cated below to separate the terminal block cover.

 HOW TO REPLACE THE SCALE PLATE

13

8

68

[68+72×(n - 1)]

+1 

 

   0

+0.7

   0

Panel thickness 2.3 – 20

13

8

+1    0

+1

   0

 PANEL CUTOUT unit: mm

• Single mounting

• Clustered mounting

n = number of units

Panel

Mounting Bracket

Pull up the part ‘A’ when replacing the scale plate.

Body

Scale Plate

A

Summary of Contents for SM10

Page 1: ...COMPONENT IDENTIFICATION 3 EXTERNAL DIMENSIONS TERMINAL ASSIGNMENTS 3 INSTALLATION 4 CONNECTION DIAGRAM 5 PREPARATION WIRING TO THE UNIT 5 LIGHTNING SURGE PROTECTION 5 SETTING FLOWCHART 6 SETTING MODE 7 MANUAL LOADER with 4 digit digital meter LED bar indicator MODEL SM10 OPERATING MANUAL ...

Page 2: ...ons subject to direct sunlight or where excessive dust dirt or metal particles are present This unit is a precision instrument Do not store or use it where large shocks or excessive vibration can occur Do not store or use this unit in environments subject to chemical evaporation such as that of organic solvents or where there are chemicals and or acids present in the environment Do not use paint t...

Page 3: ...MV bargraph meter 8 Retroactive time LED RA 9 Transition ramp rate LED RR 10 Input indication selector IND 11 CAS MAN indicator LED 12 CAS MAN selector OUT 13 Manual operation button UP 14 Acceleration button FAST Acclerates the operation by pressing simultaneously with UP or DOWN button 15 Manual operation button DOWN 14 15 16 17 18 19 20 21 22 23 24 25 26 1 2 3 4 5 6 7 8 9 10 11 12 13 40 41 42 4...

Page 4: ...enance purpose e g wiring removing or install ing HOW TO MOUNT THE UNIT ON A PANEL 1 Remove both mounting brackets 2 Detach the terminal cover and insert it first and then the module itself into the cutout hole The cover is slightly wider than the module 3 Put and slide the brackets back into the holes at the top and the bottom and tighten them until the module is firmly fixed HOW TO REMOVE THE TE...

Page 5: ...with CAS input 2 PREPARATION WIRING TO THE UNIT POWER SUPPLY Confirm the power input rating marked on the product 1 Remove the terminal cover 2 Loosen three screws at the power supply terminals 3 Connect power input and protective earth cables to them 4 Replace the terminal cover I O SIGNALS Refer to the following example of connecting CAS input sig nal 1 Turn off the power supply and remove the t...

Page 6: ... stopped 1 Mode transition Back to Measuring Mode Retroactive Time ON SETTING MODE IND IND Press IND Press Hold for 3 sec OUT Press Hold for 1 sec OUT Press Hold for 1 sec CAS Input CAS LED ON IND Press Press IND IND Press Press Transition Ramp Rate ON MV Input Back to PV input MV LED ON IND Press MEASURING MODE 1 Value before interruption is held Output Manual Switching CAS MAN LED CAS MAN LED st...

Page 7: ... next item Refer to the next page for the definitions of Retroactive Time and Transition Ramp Rate LED BRIGHTNESS range 1 2 3 1 Confirm that the unit is in the setting mode 2 Press IND button one or more times to choose the LED RA in blinking state 3 The digital meter shows the present setting 4 Use UP DOWN button to set a desired value on the digital meter 5 Press IND button to move on to the nex...

Page 8: ...cator is turned on and the MV output tracked down by the retroactive time setting 100 output at the point a in the above example is provided Though the above example shows no manual control the MV value can be changed to a desired value by manipulating UP DOWN buttons during this period 2 The manual control mode is cancelled when the manual command input is turned off Both CAS and MAN indicators t...

Reviews: