INSTRUCTION MANUAL

DC VOLTAGE / CURRENT INPUT MODULE, 4 points

(4 points, non-isolated, tension clamp terminal block)

MODEL

R80FST4NJ

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC voltage / current input module .....................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

GENERAL PRECAUTIONS

• Before you remove or mount the unit, turn off the power 

supply and output signal for safety.

• DO NOT set the switches while the power is supplied.  

The switches are used only for maintenance without the 
power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 10 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

POWER UP

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for-
satisfying complete performance described in the data-
sheet.

INSTALLATION

A

B

 HOW TO MOUNT THE MODULE ON DIN RAIL

Confirm that the locking clamps of the extension power supply module 
are set.  Insert the module in parallel to the next one while aligning the  
grooves of both modules (A & B in the above figure).
Maintain it perpendicularly to the rail. 

More I/O modules can be added in the same manner.

Summary of Contents for R80FST4NJ

Page 1: ...to ensure the CE conform ity GENERAL PRECAUTIONS Before you remove or mount the unit turn off the power supply and output signal for safety DO NOT set the switches while the power is supplied The swi...

Page 2: ...slide it straight until the hooks are latched When removing the cover pull it out while squeezing the hooks inward Groove Hook HOW TO UNMOUNT THE MODULE FROM DIN RAIL Release the locking clamps and p...

Page 3: ...ED INPUT STATUS INDICATOR LED LED OPERATION COLOR FUNCTION RUN Indicator LED ON Red Upper communication Stopping or abnormal Internal communication Abnormal ON Green Upper communication Normal Interna...

Page 4: ...h 0 15 are available for module address MODULE AD DRESS SW1 1 2 3 4 0 OFF OFF OFF OFF 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF...

Page 5: ...OR TERMINAL ASSIGNMENT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PIN No ID FUNCTION 1 Ai1 Input 1 2 AG1 Input 1 3 Excitation supply 4 Excitation supply 5 Ai2 Input 2 6 AG2 Input 2 7 Excitation supply 8 E...

Page 6: ...abled Input type DC voltage 10 10 V DC 10 10 V DC DC current 20 20 mA DC Zero fine adj 320 00 320 00 0 00 Gain fine adj 3 2000 3 2000 1 0000 Zero base depends on input types 1 10 000 V Full base depen...

Page 7: ...16 15 14 13 CONNECTOR INTERNAL BUS INTERNAL POWER EXC SUPPLY Input Connector FE WIRING INSTRUCTIONS Tension clamp terminal block Unit side connector MC1 5 16 GF 3 5 Phoenix Contact Applicable connect...

Reviews: