background image

R7ML-EC16D

P. 1 / 3

EM-7805-AA Rev.1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

PNP TRANSISTOR OUTPUT EXTENSION MODULE, 16 points

(MECHATROLINK-

I

 / -

II, 

short circuit protection)

MODEL

R7ML-EC16D

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Discrete output extension module  .................................  (1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVE

• The actual installation environments such as panel con-

figurations, connected devices and connected wires may 
affect the protection level of this unit when it is integrat-
ed in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  24V DC rating: 24V ±10%, approx. 20mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and output signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within 0 to 55°C (32 

to 131°F) with relative humidity within 30 to 90% RH in 
order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

Discrete Output Status Indicator LED

Output Terminals

 

DISCRETE OUTPUT STATUS INDICATOR LED

Discrete output extension modules have LED indicators 
showing output signal status.
  Contact ON : LED ON
  Contact OFF : LED OFF

 

OUTPUT TERMINAL ASSIGNMENT

10

+24V

11

Y1

12

Y3

1

0V

2

Y0

3

Y2

13

Y5

4

Y4

14

Y7

5

Y6

15

Y9

6

Y8

16

YB

7

YA

17

YD

8

YC

9

YE

18

YF

NO.

ID

FUNCTION

NO.

ID

FUNTION

1

0V

0V

10

+24V 24V DC (common)

2

Y0

Output 0

11

Y1

Output 1

3

Y2

Output 2

12

Y3

Output 3

4

Y4

Output 4

13

Y5

Output 5

5

Y6

Output 6

14

Y7

Output 7

6

Y8

Output 8

15

Y9

Output 9

7

YA

Output 10

16

YB

Output 11

8

YC

Output 12

17

YD

Output 13

9

YE

Output 14

18

YF

Output 15