background image

R3-NMW1F

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8286  P. 9 / 10

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

Shows each module’s availability and error status.

0

15

Module 1
Module 2
Module 3
      :
Module 16

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

 

ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4 and US4, etc.)

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
-15 to 0 % is a negative range represented in 2’s complement.
In case of R3-US4, -10 to 0% is a negative range represented in 2’s complement.

0

15

 

TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4 and US4, etc.)

16-bit binary data.
With °C  temperature unit, raw data is multiplied by 10.  For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.  For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

0

15

 

ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)

16-bit binary data.
Integer obtained by multiplying unit value (A) by 100.
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.

0

15

 

ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)

32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
32-bit data cannot be accessed using floating addresses.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

Summary of Contents for R3-NMW1F

Page 1: ...cles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical...

Page 2: ...s own expense This transmitter must not be co located or operated in conjunction with any other antenna or transmitter FCC RF EXPOSURE INFORMATION This equipment complies with FCC radiation exposure l...

Page 3: ...SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 2 Refer to the specifications...

Page 4: ...selectable up to 10 channels 0 Short address 0000 invalid 0001 to FFFD hexadecimal 4 digits 0000 Network name English one byte characters within 16 characters one byte space _ are usable Blank Encrypt...

Page 5: ...S Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 109 4 29 45 1 77 200 7 87 TERMINAL COVER 109 4 29 2500 98 43 Dia 3 12 Dia 1 2 05 Dia 27 1 06 36 1 42 80 3 15 WITH SLEEVE ANT...

Page 6: ...rawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Recommended manufacturer Japan Solderless Terminal M...

Page 7: ...ad write 07 Read Exception Status 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter 12 Fetch Comm Event Log 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digit...

Page 8: ...t corresponding to such module turns to 1 Main Sub Switching Commands given to the network modules result as follows MAIN MODULE SUB MODULE OUTPUT MODE 1 0 Main bus is used Red LED turns on at RUN LED...

Page 9: ...nt 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature u...

Page 10: ...1025 0 Address 01025 1 R3 sub network main sub switching control 1 2 3 4 5 1 When the main sub switching control for both main and sub network is set to 0 all contact outputs are off and analog output...

Reviews: