background image

R3-NMW1F

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8286  P. 8 / 10

MODBUS I/O ASSIGNMENTS

ADDRESS

DATA FORMAT NAME

Coil (0X)

1 – 1024

Digital Output (discrete output)

1025

Main / Sub Switching Command (valid only with SW3-3 set to ON)

Inputs (1X)

1 – 1024

Digital Input (discrete input)

1025 – 1040

Module Status

1041 – 1056

Error Status

1057 – 1072

Data Error Status

Input Registers (3X)

1 – 256

I

Analog Input

257 – 768

F

Analog Input

Holding Registers (4X)

1 – 256

I

Analog Output

257 – 768

F

Analog Output

I: Integer, 0 – 10000 (0 – 100%)
F: Floating (32-bit data cannot be accessed using floating addresses.)
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.

• Module Status indicates whether individual I/O modules are mounted or not.  The bit corresponding to the mounted slot 

turns to “1,” and the unmounted slot to “0.”

• Error Status indicates error status for each module as described below.  The bit corresponding to such module turns to “1.”

  R3-TSx, R3-RSx, R3-US4: Input burnout
  R3-DA16A: Power input in error or disconnected
  R3-YSx: Output current error (e.g. load unconnected)

• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each 

module.  The bit corresponding to such module turns to “1.”

• Main / Sub Switching Commands given to the network modules result as follows:

‘MAIN’ MODULE

‘SUB’ MODULE

OUTPUT MODE

1

0

Main bus is used; Red LED turns on at RUN LED of the I/O modules.

0

1

Sub bus is used; Green LED turns on at RUN LED of the I/O modules.

1

1

Main bus is used; Amber LED turns on at RUN LED of the I/O modules.

0

0

Output is invalid; RUN LED of the I/O modules turns off.

• Writing to Coil (0X) and Holding Registers (4X) is only available with either Wireless or Modbus communication.  It is 

available to change the configuration with Configurator Software (model: R3CON).  Factory default setting is Modbus com-
munication.

TRANSMISSION DATA ASSIGNMENTS

DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     

Module 1 

 

4

     

Module 2 

 

4

     

Module 3 

 

4

     

Module 4 

 

1

     

Module 5 

 

1

     

Module 6 

 

1

     

Module 7 

 

1

Then the I/O data are assigned as in the table below:

ADDRESS

POSITION

ADDRESS

POSITION

Input Registers (3X)
Holding Registers (4X)

1 – 4, 257 – 264

Slot 1

Coil (0X)
Inputs (1X)

1 – 64

Slot 1

5 – 8, 265 – 272

Slot 2

65 – 128

Slot 2

9 – 12, 273 – 280

Slot 3

129 – 192

Slot 3

13, 281 – 282

Slot 4

193 – 208

Slot 4

14, 283 – 284

Slot 5

209 – 224

Slot 5

15, 285 – 286

Slot 6

225 – 240

Slot 6

16, 287 – 288

Slot 7

241 – 256

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned 
data areas (Data Allocation Type) are allotted with the Data 
Allocation Type ‘1’ and ‘4.’ With ‘8’ and ‘16,’ 64 (4 × 16) are 
automatically allotted.

Summary of Contents for R3-NMW1F

Page 1: ...cles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical...

Page 2: ...s own expense This transmitter must not be co located or operated in conjunction with any other antenna or transmitter FCC RF EXPOSURE INFORMATION This equipment complies with FCC radiation exposure l...

Page 3: ...SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 2 Refer to the specifications...

Page 4: ...selectable up to 10 channels 0 Short address 0000 invalid 0001 to FFFD hexadecimal 4 digits 0000 Network name English one byte characters within 16 characters one byte space _ are usable Blank Encrypt...

Page 5: ...S Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 109 4 29 45 1 77 200 7 87 TERMINAL COVER 109 4 29 2500 98 43 Dia 3 12 Dia 1 2 05 Dia 27 1 06 36 1 42 80 3 15 WITH SLEEVE ANT...

Page 6: ...rawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Recommended manufacturer Japan Solderless Terminal M...

Page 7: ...ad write 07 Read Exception Status 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter 12 Fetch Comm Event Log 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digit...

Page 8: ...t corresponding to such module turns to 1 Main Sub Switching Commands given to the network modules result as follows MAIN MODULE SUB MODULE OUTPUT MODE 1 0 Main bus is used Red LED turns on at RUN LED...

Page 9: ...nt 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature u...

Page 10: ...1025 0 Address 01025 1 R3 sub network main sub switching control 1 2 3 4 5 1 When the main sub switching control for both main and sub network is set to 0 all contact outputs are off and analog output...

Reviews: