R3-NM3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8330  Rev.3  P. 9 / 9

 

MAIN / SUB SWITCHING CONTROL

Address : 01025 = 0

Communication Status

Start

Main Lost

Main Restored

Switching by Host

Address : 01025 = 1

R3 main network
(main/sub switching control)

Address : 01025 = 0

Address : 01025 = 1

R3 sub network
(main/sub switching control)

(1)

(2)

(3)

(4)

(5)

1) When the main/sub switching control for both main and sub network is set to ‘0,’ all contact outputs are off, and analog 

output modules output -15%.

2) When the main’s setting is switched to ‘1,’ the output modules are in control of the main host device.
3) When a loss of communication is detected in the main network, the output signal is held for the preset time period. (Timer 

is programmable with the PC Configurator Software, R3CON.)  After the time has been elapsed, the output control is 

switched from the main to the sub network.  Be sure to set an appropriate output signal to the sub network and switch the 

sub’s setting to ‘1’ before such switching occurs.

4) The output modules’ control does not automatically switched back to the main’s when the main network is restored if the 

main’s setting is ‘0.’  Be sure to switch the setting back to ‘1’ before the communication is restored.

5) When both the main and the sub network modules are in communication, the output can be switched without delay.

Summary of Contents for R3-NM3

Page 1: ...r install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temp...

Page 2: ...1 Bit assignment according to Parity and Data Mode setting MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 Note Be sure to set unused SW6 6 through 6 8 to OFF SIDE DIP SW...

Page 3: ...used when the switching control is set to Host In Normal mode Main bus is normally used while Sub bus is when the main communication has failed Be sure to match this control mode for both network mod...

Page 4: ...conductor terminal 1 4 2 3 6 RUN RUN RUN CONTACT OUTPUT U V POWER INPUT WIRING INSTRUCTIONS M3 SCREW TERMINAL power input RUN contact output Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing be...

Page 5: ...Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave type R...

Page 6: ...to the mounted slots turns to 1 and the unmounted slots to 0 Error Status indicates error status for each module as described below The bit corresponding to such modules turns to 1 R3 TSx R3 RSx R3 US...

Page 7: ...ssigned data areas Data Allocation Type are allotted with the Data Al location Type 1 and 4 With 8 and 16 64 4 16 are automatically assigned MODULE STATUS ERROR STATUS DATA ERROR STATUS Shows each mod...

Page 8: ...tions Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 32 bit data cannot be accessed using floating addresses 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits BCD D...

Page 9: ...1 the output modules are in control of the main host device 3 When a loss of communication is detected in the main network the output signal is held for the preset time period Timer is programmable wi...