background image

R3-NM3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8330  Rev.3  P. 7 / 9

TRANSMISSION DATA ASSIGNMENTS

DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     

Module 1 

 

4

     

Module 2 

 

4

     

Module 3 

 

4

     

Module 4 

 

1

     

Module 5 

 

1

     

Module 6 

 

1

     

Module 7 

 

1

Then the I/O data are assigned as in the table below:

ADDRESS

POSITION

ADDRESS

POSITION

Input Registers (3X)
Holding Registers (4X)

1 – 4, 257 – 264

Slot 1

Coil (0X)
Inputs (1X)

1 – 64

Slot 1

5 – 8, 265 – 272

Slot 2

65 – 128

Slot 2

9 – 12, 273 – 280

Slot 3

129 – 192

Slot 3

13, 281 – 282

Slot 4

193 – 208

Slot 4

14, 283 – 284

Slot 5

209 – 224

Slot 5

15, 285 – 286

Slot 6

225 – 240

Slot 6

16, 287 – 288

Slot 7

241 – 256

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned data areas (Data Allocation Type) are allotted with the Data Al-
location Type ‘1’ and ‘4.’ With ‘8’ and ‘16,’ 64 (4 × 16) are automatically assigned.

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

Shows each module’s availability and error status.

0

15

Module 1
Module 2
Module 3
      :
Module 16

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

 

ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4 and US4, etc.)

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  Negative percentage is represented in 2’s 
complements.

0

15

 

TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4 and US4, etc.)

16-bit binary data.
With °C  temperature unit, raw data is multiplied by 10.  For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.  For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

0

15

Summary of Contents for R3-NM3

Page 1: ...r install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temp...

Page 2: ...1 Bit assignment according to Parity and Data Mode setting MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 Note Be sure to set unused SW6 6 through 6 8 to OFF SIDE DIP SW...

Page 3: ...used when the switching control is set to Host In Normal mode Main bus is normally used while Sub bus is when the main communication has failed Be sure to match this control mode for both network mod...

Page 4: ...conductor terminal 1 4 2 3 6 RUN RUN RUN CONTACT OUTPUT U V POWER INPUT WIRING INSTRUCTIONS M3 SCREW TERMINAL power input RUN contact output Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing be...

Page 5: ...Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave type R...

Page 6: ...to the mounted slots turns to 1 and the unmounted slots to 0 Error Status indicates error status for each module as described below The bit corresponding to such modules turns to 1 R3 TSx R3 RSx R3 US...

Page 7: ...ssigned data areas Data Allocation Type are allotted with the Data Al location Type 1 and 4 With 8 and 16 64 4 16 are automatically assigned MODULE STATUS ERROR STATUS DATA ERROR STATUS Shows each mod...

Page 8: ...tions Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 32 bit data cannot be accessed using floating addresses 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits BCD D...

Page 9: ...1 the output modules are in control of the main host device 3 When a loss of communication is detected in the main network the output signal is held for the preset time period Timer is programmable wi...

Reviews: