R3-NM3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8330  Rev.3  P. 5 / 9

MODBUS FUNCTION CODES & SUPPORTED CODES

 

Data and Control Functions

CODE NAME

01

Read Coil Status

X

Digital output from the slave

02

Read Input Status

X

Status of digital inputs to the slave

03

Read Holding Registers

X

General purpose register within the slave

04

Read Input Registers

X

Collected data from the field by the slave

05

Force Single Coil

X

Digital output from the slave

06

Preset Single Registers

X

General purpose register within the slave

07

Read Exception Status

08

Diagnostics

X

09

Program 484

10

Poll 484

11

Fetch Comm. Event Counter

X

Fetch a status word and an event counter

12

Fetch Comm. Event Log

X

A status word, an event counter, a message count and a field of event bytes

13

Program Controller

14

Poll Controller

15

Force Multiple Coils

X

Digital output from the slave

16

Preset Multiple Registers

X

General purpose register within the slave

17

Report Slave ID

X

Slave type / ‘RUN’ status

18

Program 884/M84

19

Reset Comm. Link

20

Read General Reference

21

Write General Reference

22

Mask Write 4X Register

23

Read/Write 4X Register

24

Read FIFO Queue

 

Exception Codes

CODE NAME

01

Illegal Function

X

Function code is not allowable for the slave

02

Illegal Data Address

X

Address is not available within the slave

03

Illegal Data Value

X

Data is not valid for the function

04

Slave Device Failure

05

Acknowledge

06

Slave Device Busy

07

Negative Acknowledge

08

Memory Parity Error

 

Diagnostic Subfunctions

CODE NAME

00

Return Query Data

X

Loop back test

01

Restart Comm. Option

X

Reset the slave and clear all counters

02

Return Diagnostic Register

X

Contents of the diagnostic data (2 bytes)

03

Change ASCII Input Delimiter

X

Delimiter character of ASCII message

04

Force Listen Only Mode

X

Force the slave into Listen Only Mode

Summary of Contents for R3-NM3

Page 1: ...r install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temp...

Page 2: ...1 Bit assignment according to Parity and Data Mode setting MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 Note Be sure to set unused SW6 6 through 6 8 to OFF SIDE DIP SW...

Page 3: ...used when the switching control is set to Host In Normal mode Main bus is normally used while Sub bus is when the main communication has failed Be sure to match this control mode for both network mod...

Page 4: ...conductor terminal 1 4 2 3 6 RUN RUN RUN CONTACT OUTPUT U V POWER INPUT WIRING INSTRUCTIONS M3 SCREW TERMINAL power input RUN contact output Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing be...

Page 5: ...Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave type R...

Page 6: ...to the mounted slots turns to 1 and the unmounted slots to 0 Error Status indicates error status for each module as described below The bit corresponding to such modules turns to 1 R3 TSx R3 RSx R3 US...

Page 7: ...ssigned data areas Data Allocation Type are allotted with the Data Al location Type 1 and 4 With 8 and 16 64 4 16 are automatically assigned MODULE STATUS ERROR STATUS DATA ERROR STATUS Shows each mod...

Page 8: ...tions Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 32 bit data cannot be accessed using floating addresses 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits BCD D...

Page 9: ...1 the output modules are in control of the main host device 3 When a loss of communication is detected in the main network the output signal is held for the preset time period Timer is programmable wi...

Reviews: