• Input Error Data: SW3-2

Hold

: When the communication from an input module is lost 

due to the input module error, the network module holds the 
signal and stands by until the communication recovers.

Set to ‘0’

: When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD 

(*)

SET  ‘0’

SW3-2

OFF

ON

• Main/Sub Switching Control: SW3-3

The host PC or PLC can choose whether ‘Main’ or ‘Sub’ bus 
is used when the switching control is set to ‘Host.’
In ‘Normal’ mode, ‘Main’ bus is normally used, while ‘Sub’ 
bus is when the main communication has failed.
Be sure to match this control mode for both network mod-
ules in dual communication mode.

SW

MAIN/SUB SWITCHING CONTROL

NORMAL 

(*)

HOST

SW3-3

OFF

ON

Note: Set SW3-3 to OFF for use in single communication mode.

• LED Function: SW3-4

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED FUNCTION

RUN

ERR

OFF (*)

Green when normal

Green when abnormal

ON

Red when receiving

Red when transmitting

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.

 

NETWORK MODULE SETTING 

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Time (no communication time)

0.2 – 3200.0 (sec.)

3.0 (sec.) 

Summary of Contents for R3-NM3

Page 1: ...r install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temp...

Page 2: ...1 Bit assignment according to Parity and Data Mode setting MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 Note Be sure to set unused SW6 6 through 6 8 to OFF SIDE DIP SW...

Page 3: ...used when the switching control is set to Host In Normal mode Main bus is normally used while Sub bus is when the main communication has failed Be sure to match this control mode for both network mod...

Page 4: ...conductor terminal 1 4 2 3 6 RUN RUN RUN CONTACT OUTPUT U V POWER INPUT WIRING INSTRUCTIONS M3 SCREW TERMINAL power input RUN contact output Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing be...

Page 5: ...Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave type R...

Page 6: ...to the mounted slots turns to 1 and the unmounted slots to 0 Error Status indicates error status for each module as described below The bit corresponding to such modules turns to 1 R3 TSx R3 RSx R3 US...

Page 7: ...ssigned data areas Data Allocation Type are allotted with the Data Al location Type 1 and 4 With 8 and 16 64 4 16 are automatically assigned MODULE STATUS ERROR STATUS DATA ERROR STATUS Shows each mod...

Page 8: ...tions Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 32 bit data cannot be accessed using floating addresses 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits BCD D...

Page 9: ...1 the output modules are in control of the main host device 3 When a loss of communication is detected in the main network the output signal is held for the preset time period Timer is programmable wi...

Reviews: