5.  INSTALLATION

The following is a general procedure for mounting the 
MSPxC to a valve with a yoke and coupling.
Be sure NOT TO CHANGE factory adjusted setting of the 
MSPxC.
Remove power supply during the procedure unless other-
wise specified.

1) Supply power to the actuator and manually control the 

actuator stem to the longest position.

2) Push in the valve stem at the lowest position.
3) Set the yoke to the actuator.
4) Push the valve stem into the actuator stem until there is 

no gap between them.

  If you need to seal the valve, leave a spring contraction 

shown in Table 3 (for example, 0.5 mm for MSP4C-x3).

5) Fix the actuator stem and valve stem with a lock nut.
6) Supply power to the actuator again and raise (retract) 

the actuator stem by several millimeters.  Check that the 

opening between the yoke and valve bonnet is closed.  Fix 

the yoke and valve.

7) Attach the position indicator if required.

MSPxC

Bolt (M5)

Position Indicator

Yoke

Actuator Stem

Lock Nut

Valve Stem

Valve Bonnet

Adjust the opening

Figure 7. MSP×C mounted onto a valve (example)

 

STEM BUTTON

ø9 (.35)

R1

ø14 (.55)

6 (.24)

4 (.16)

40°

Figure 8. Stem Details

1 (.04)

16 (.63)

ø15 (.59)

ø15 (.59)

ø10

(.39)

140°

40°

6 (.24)

Figure 9. Indicator Details

6.  WIRING CONNECTION

 

CC-Link CONNECTOR

Use a 5-core micro-style connector, female (e.g. Woodhead 
CC-Link Micro-Change), and cable approved for CC-Link.

 

POWER INPUT CONNECTOR

Use a 4-core micro-style connector, female (e.g. OMRON 
XS2F or XS2WD42).
Recommended T-shape adaptor, if necessary, is OMRON 
XR2R-D427-5.

 

TERMINATING RESISTOR

Recommended terminating resistor (connector) is Wood-
head CC150.

MSP4C / MSP5C / MSP6C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4862  Rev.1  P. 5 / 9

Summary of Contents for MSP4C

Page 1: ...7 1 1 GENERAL PROCEDURE 6 7 1 2 ZERO SPAN 6 7 1 3 DEADBAND 6 7 1 4 RESTART LIMITING TIME 6 7 1 5 COMMUNICATION ERROR OPERATION 7 7 2 CC Link 7 7 2 1 STATION NO 7 7 2 2 BAUD RATE 7 7 2 3 COMMUNICATIONS...

Page 2: ...together with mains supply ca bles or high voltage cables Do not install them in the same duct OUTDOOR USE When installing the MSPxC outdoor or where it is ex posed to rain or water drops be sure to f...

Page 3: ...R XS2M D424 2 OMRON PIN ASSIGNMENT 1 24 V 2 Not used 3 GND 4 Not used COMMUNICATION MONITOR INDICATOR LED ID STATUS MEANING L RUN ON Communicating Blink OFF Not entering the network yet Timeout L ERR...

Page 4: ...signals 25 50 75 100 0 INPUT Adjustable SPAN at ZERO CCW counterclockwise Adjustable SPAN at ZERO CW clockwise 0 25 50 75 100 OUTPUT STEM POSITION SPAN CCW ZERO CW ZERO CCW SPAN CW Adjustable SPAN Ad...

Page 5: ...Check that the opening between the yoke and valve bonnet is closed Fix the yoke and valve 7 Attach the position indicator if required MSPxC Bolt M5 Position Indicator Yoke Actuator Stem Lock Nut Valve...

Page 6: ...acted position valve s extended position is ad equate For three way valves the sealing pressure can be adjust ed to be applied in the direction where the output stem is fully retracted not available f...

Page 7: ...Forced Open Position Input 1 0 Disable 1 Position 100 RY2 RY3 RY4 RY5 RY6 RY7 RY8 Enable Target Position Input 0 Disable 1 Enable RY9 RYA Reset Motor Deadlock Alarm Motor deadlock alarm is canceled w...

Page 8: ...ed 16 bit data representing 0 01 by 1 LSB Set Enable Target Position Input to 1 Set Target Position Input For example set 5000 in binary for 50 setpoint Set 50 for 0 5 Binary must be 2 s complement Po...

Page 9: ...perated run a test operation regularly once a week for example to check proper functions 9 TROUBLESHOOTING TROUBLE L RUN L ERR POSSIBLE CAUSE HOW TO PROCEED No Func tion ON OFF Normal communication Co...

Reviews: