background image

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Lightning surge protector 

(body + arrester power relay) .........................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, and basic main-
tenance procedure.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

The model MMH, designed specifically for power require-
ments of medium capacities (10 or 30 amps), protects elec-
tronic equipment from lightning surges induced through 
power cables.
Conventional lightning arrester utilizes a fuse to prevent 
fire when it is damaged by surges far more exceeding its 
capacity.  It shuts the power supply line off, and eventually 
affects overall plant operations.
The MMH, on the other hand, only separates the damaged 
arrester module model MEH from the line by driving the 
power relay.
When a leakage current detected inside the MEH exceeds 
approx. 100mA, the MMH drives and latches the power 
relay, which is indicated by closed alarm contact and red 
ALARM LED on the front.
The alarm contact is reset when the MEH is removed from 
its socket or when the power is turned off.
When the alarm is indicated, the surge voltage between 
lines is increased up to 800V. Replace the MEH with a new 
one as soon as possible.

 

SPECIFICATIONS

BETWEEN LINES

LINE TO 

GND

MMH-1

MMH-2

Discharge voltage

130V AC min. 285V AC min. 285V AC min.

Max. surge volt. (p-p)* 350V max. 700V max. 800V max.
Leakage current

≤50mA

@110V AC

≤30mA

@220V AC

≤1mA

@220V AC

Response time

≤0.01 µsec.

Discharge current

 10000A (8 / 20 µsec.)

Max. load current

 10A (MMH-x10) or 30A (MMH-x30)

Voltage drop

≤1V (50/60 Hz)

*The maximum voltage that could pass through M-RESTER. 
Protected equipment must be able to withstand this voltage 
for a very short time period.

POINTS OF CAUTION

 

ENVIRONMENT

• When heavy dust or metal particles are present in the at-

mosphere, install M-RESTER inside proper housing and 
ventilate it.

• Do not install the M-RESTER where it is subjected to 

continuous vibration. Do not apply physical impact to the 
M-RESTER.

• Environmental temperature must be within -5 to +55°C 

and humidity within 30 – 90% RH in order to ensure ad-
equate life span and operation.

 

DIELECTRIC STRENGTH TEST

• DO NOT perform dielectric strength tests for the MMH.  

The arrester module is grounded to the metallic hous-
ing inside the unit.  The discharge element will start 
discharging between line and ground when a dielectric 
strength test is performed.

 

RATED CURRENT

• Be sure that the rated current of protected equipment 

does not exceed the maximum load current specification 
of the M-RESTER.

• Be sure to install a breaker which matches the current 

rating at the power supply side of the M-RESTER.

 

ALARM CONTACT

• During NORMAL operation, it is possible for the ALARM 

LED to remain OFF and the ALARM contact to turn ON 
momentarily when experiencing lightning surges.  Please 
continue use of the unit as this is standard operation.

LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE

(10 – 30A; replaceable arrester module)

MODEL

MMH

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8179  Rev.4  P. 1 / 4

INSTRUCTION MANUAL

Summary of Contents for MMH-1

Page 1: ...surge voltage between lines is increased up to 800V Replace the MEH with a new one as soon as possible SPECIFICATIONS BETWEEN LINES LINE TO GND MMH 1 MMH 2 Discharge voltage 130V AC min 285V AC min 285V AC min Max surge volt p p 350V max 700V max 800V max Leakage current 50mA 110V AC 30mA 220V AC 1mA 220V AC Response time 0 01 µsec Discharge current 10000A 8 20 µsec Max load current 10A MMH x10 or...

Page 2: ...ted equipment side Power Relay Arrester Module model MEH FRONT PANEL CONFIGURATION ARRESTER MODULE model MEH ALARM LED RUN LED Specification Label for MEH top The MEH s model suffix codes change according to the power input voltage Check the specification on the label MMH 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 81...

Page 3: ...ground terminal of the protected equipment 100Ω max 6 4 3 G 5 1 2 U V B BREAKER AC POWER SOURCE Be sure to install a breaker M RESTER PROTECTED EQUIPMENT ALARM Turns on at the alarm condition 7 GROUNDING M RESTER PROTECTED EQUIPMENT G G CROSSOVER WIRE GROUNDING 100 ohms or less A crossover wire between M RESTER ground and ground or metallic housing of equipment is required for protection If the pr...

Page 4: ...s standard operation B RUN LED If the RUN LED green remains OFF when you turned the power supply ON replace the MEH C Wiring Make sure that the terminal 3 is connected to the me tallic housing of the unit and that of protected equipment D Discharge Function of the MEH Remove the MEH and test its discharge capability as fol lows Check resistance across the following terminals 3 4 3 6 4 6 infinite s...

Reviews: