background image

MDR-8

P. 1 / 2

EM-8131  Rev.6

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

BEFORE USE ....

Thank you for choosing M-System.  Before use, check the package 
you received as below.
If you have any problems or questions on the product, please 
contact M-System's Sales Office or representatives.

PACKAGE INCLUDES:

  Lightning surge protector ................................................. (1)

MODEL NO.

Check that model No. described on specification label is exactly 
what you ordered.

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when you 
use this product, installation, and basic maintenance procedure.

LIMITATION APPLICABLE TO M-RESTER

The M-Rester will protect electronics equipment from damage 
caused by lightning by absorbing most of the surge voltages.

However, M-Rester may not be effective against certain 
extremely high voltages caused by a direct or almost direct 
hit by lightning.

M-Rester must be installed according to this installation / 
instruction manual.

GENERAL

FUNCTION & FEATURES

• Designed specifically for ON-OFF signals, protecting semicon-
ductor switches used for ON-OFF outputs from the computer 
or PLC from lightning surge damage that enters on the wiring 
between these instruments • 8 channels • Most convenient as 
junction board • Minimum mounting space

SPECIFICATIONS

BTWN LINES

LINE TO COM

LINE/COM TO G

Discharge voltage

±30V min.

30V min.

±60V min.

Max. surge voltage*

±40V max.

40V max.

±650V max.

Leakage current

≤5µA

@±30V DC

≤5µA

@30V DC

≤5µA

@±60V DC

Response time

≤0.1 µsec.

Discharge current

1000A (8 / 20 µsec.)

Max. load current

100mA

Int. series resistance

approx. 100Ω

*The maximum voltage that could pass through M-RESTER.  Pro-
tected equipment must be able to withstand this voltage for a very 
short time period.

POINTS OF CAUTION

 

n

ENVIRONMENT

• Indoor Use
• When heavy dust or metal particles are present in the at-

mosphere, install M-RESTER inside proper housing and 
ventilate it.

• Do not install the M-RESTER where it is subjected to 

continuous vibration. Do not apply physical impact to the 
M-RESTER.

• Environmental temperature must be within -5 to +55°C 

(23 to 131°F) and relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

n

DIELECTRIC STRENGTH TEST

• DO NOT perform dielectric strength tests with wires con-

nected to the unit. Otherwise the element will start discharg-
ing at discharge voltage, which can cause insulation failure. 
Be sure to return the wires after the test.

 

n

AND ....

• We recommend that you keep spare M-RESTERs so that 

you can replace them when necessary.

• Lightning surge can enter not only through signal lines 

but also through power supply lines. We recommend that 
you also use the Lightning Arrester for Power Lines for 
sufficient protection.

COMPONENT IDENTIFICATION

REAR VIEW

SURGE

SIDE

S1
S2
S3
S4
S5
S6
S7
S8

COM

GND

PROTECT

SIDE

P1
P2
P3
P4
P5
P6
P7
P8
COM
GND

Body

Specification Label

INSTRUCTION MANUAL

MULTI M-RESTER

MODEL

MDR-8

Reviews: