MDP-PM

P. 1 / 3

EM-8115 Rev.7

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

LIGHTNING SURGE PROTECTOR FOR 

POTENTIOMETER USE

MODEL

MDP-PM

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Surge protector ............................................................. (1)

 MODEL NO.

Confirm that the model number described on the product is 
exactly what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-Rester will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-Rester may not be effective against certain 
extremely high voltages caused by a direct or almost di-
rect hit by lightning.
M-Rester must be installed according to this installation 
/ instruction manual.

CAUTION (DISCHARGE CAPACITY)

The discharge capacity 
of this unit has been in-
creased to 5000 Amps.  
However, using an older 
style base socket with 
any upgraded head ele-
ment could decrease the 
overall effectiveness of 
the unit.
The upgraded version 
element and socket are 
distinguished by blue labels affixed to them.  If you are re-
placing the head element only, be sure to check the label 
color of the base socket that is already installed.

GENERAL

 FUNCTION & FEATURES

• Designed  specifically  for  potentiometer  or  slidewire  cir

-

cuits

• Protects potentiometer transmitters from lightning surge 

damage that enters on the wiring between the potentiom-
eter and the transmitter

• Absorbs  surges  only  without  affecting  instrumentation 

signal

• 

No interruption of signal by unplugging the protector element

 SPECIFICATIONS

POINTS OF CAUTION

 ENVIRONMENT

• When heavy dust or metal particles are present in the air, 

install the surge protector inside proper housing with suf-
ficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 

impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

 DIELECTRIC STRENGTH TEST

• Loosen the screw located at the left-center of the element 

and remove the element module from the base before 
conducting a dielectric strength testing.  Otherwise the 
element will start discharging at a voltage exceeding the 
max. continuous operating voltage (Uc), which can cause 
insulation failure of the module.

  Be sure to return the element and fasten securely after 

the test.

 AND ....

• We  recommend  that  you  keep  spare  surge  protectors  so 

that you can replace them when necessary.

• Lightning surge can enter not only through signal lines 

but also through power supply lines.  We recommend that 

you also use the surge protectors for power line for suf-
ficient protection.

M•RESTER

New Element Label

Blue:  5000A
(Black: 2000A)

New Base Label

Blue:  5000A
(White: 2000A)

 

LINE TO LINE

 

LINE TO 

 

 EARTH

Max. continuous 

±7.5V 

7.5V 

±140V 

operating voltage (Uc) 

B – C 

B or C – A

Voltage protection level  ±16V max  16V max  ±650V max 

(Up) @1kV (100A) 

2 – 3 

2 or 3 – 1

Voltage protection level  ±25V max  25V max  ±800V max 

(Up) @2kV (1kA) 

2 – 3 

2 or 3 – 1

Leakage current 

≤10µA 

≤10µA 

≤10µA 

 

@±7.5V DC  @7.5V DC  @±140V DC 

 

B – C 

B or C – A

Capacitance @1 MHz 

≤2000 pF 

≤100 pF

Response time 

≤0.1 microsecond

Max. discharge current

  

5000A (8 / 20 µs) 

 

(Imax) 
Nominal current (I

N

) 100mA

Internal series resistance

  10Ω ±0.1%, 30 ppm/°C (17 ppm/°F)