LIGHTNING SURGE PROTECTOR FOR

PHOTOVOLTAIC SYSTEM, INSTRUMENT SHELTER

MODEL

MDP-200T

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Surge protector ............................................................. (1)
  DIN rail mounting adaptor* ........................................ (1)
  Screws for mounting (M4 

× 

8)* .................................... (2)

  *Included with option code /A33

 MODEL NO.

Confirm that the model number described on the product is 
exactly what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-Rester will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-Rester may not be effective against certain 
extremely high voltages caused by a direct or almost di-
rect hit by lightning.
M-Rester must be installed according to this installation 
/ instruction manual.

GENERAL

 FUNCTION & FEATURES

• Designed for AC and specifically for DC power supplies up 

to 1 amp.

• Beneficial  for  protecting  instruments  from  counter  elec

-

tromotive force by inductors and of course normal light-
ning surges entering from power supply lines.

• 1A fuse incorporated in element circuit.

 SPECIFICATIONS

LINE TO LINE

LINE TO EARTH

Max. line voltage (Uc)

250V AC

350V DC

----

Discharge voltage

410V min

410V min

Voltage protection level (Up)

800V max

800V max

Leakage current

≤0.15mA

@300V DC

≤0.15mA

@300V DC

Response time

≤0.1 microsecond

Max. discharge current (Imax) 

1000A (8 / 20 µs)

Nominal current (I

N

)

1.0A

Internal series resistance

≤0.4Ω including return

Dielectric strength of the 
base module

1500V AC @1 minute

(G terminal to other terminals)

POINTS OF CAUTION

 ENVIRONMENT

• When heavy dust or metal particles are present in the air, 

install the surge protector inside proper housing with suf-
ficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 

impact.

• Environmental temperature must be within -20 to +80°C     

(-4 to 176°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

 DIELECTRIC STRENGTH TEST

• Loosen the screw located at the left-center of the element 

and remove the element module from the base before 
conducting a dielectric strength testing.  Otherwise the 
element will start discharging at a voltage exceeding the 
max. continuous operating voltage (Uc), which can cause 
insulation failure of the module.

  Be sure to return the element and fasten securely after 

the test.

 AND ....

• We  recommend  that  you  keep  spare  surge  protectors  so 

that you can replace them when necessary.

• Lightning surge can enter not only through signal lines 

but also through power supply lines.  We recommend that 

you also use the surge protectors for power line for suf-
ficient protection.