INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR

STANDARD SIGNAL LINE

 (ultra-slim)

MODEL

MD7ST

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
When using this product in potentially explosive atmos-
phere or hazardous (classified) location, you have to follow
the safety procedure to install it.  Please refer to “SAFE IN-
STALLATION MANUAL” for each type of certification.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• 

High discharge current capacity 20 kA (8 / 20 µs), 1 kA
(10 / 350 µs)

• 

Ultra-thin 7-mm-wide module can be mounted in high
density

• 

Excellent protection employing multi-stage SPD circuits

• 

DIN rail mounting and grounding

• 

Shield terminal provided

 

SPECIFICATIONS

See Table 1.

Table 1. Specifications

MODEL NO.

NOMINAL VOLTAGE

MD7ST-24

MD7ST-60

SHLD TERMINAL

FF

FG

GF

GG

FF

FG

GF

GG

Max. continuous
operating voltage
(Uc)

Line to Line

30V

70V

Line to Earth

±160V

30V

±160V

70V

Line to SHLD

±160V

30V

±160V

70V

SHLD to Earth

±160V

short

±160V

short

±160V

short

±160V

short

Voltage protection
level (Up)
@4kV (1.2 / 50 µs)

Line to Line

60V

115V

Line to Earth

±800V

±60V

±800V

±115V

Line to SHLD

±1200V

±800V

±60V

±1200V

±800V

±115V

SHLD to Earth

±800V

short

±800V

short

±800V

short

±800V

short

Leakage current
@Uc

Line to Line

≤5µA

≤5µA

Other sections

≤5µA

≤5µA

Response time

Line to Line

≤4 nsec.

≤4 nsec.

Other sections

≤20 nsec.

≤20 nsec.

Max. discharge current (Imax)

20kA (8 / 20 µs), 1.0kA (10 / 350 µs)

Nominal current (I

N

)

250mA

Internal series
resistance

Without fuse

4.7Ω ±10% per line

10Ω ±10% per line

With fuse

7.5Ω ±10% per line

12.5Ω ±10% per line

056 222 38 18

[email protected]

www.sentronic.com