EM-8062  Rev.4  P. 1 / 5

INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR

PULSE SIGNAL

 (ultra-slim)

MODEL

MD7PL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
When using this product in potentially explosive atmos-
phere or hazardous (classified) location, you have to follow
the safety procedure to install it.  Please refer to “SAFE IN-
STALLATION MANUAL” for each type of certification.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• 

High discharge current capacity 20 kA (8 / 20 µs), 1 kA
(10 / 350 µs)

• 

Ultra-thin 7-mm-wide module can be mounted in high
density

• 

Excellent protection employing multi-stage SPD circuits

• 

DIN rail mounting and grounding

• 

Shield terminal provided

• 

Protects two pulse signal lines

 

SPECIFICATIONS

See Table 1.

POINTS OF CAUTION

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.

• 

Do not install the unit where it is subjected to continuous
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -25 to +85°C
(-13 to +185°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.

• 

This unit needs a DIN rail as earth grounding bar.  Ox-
ide coating of an aluminium rail may lower the electric
conductivity between this module and the ground.  Use a
steel or copper rail.

Table 1. Specifications

MODEL NO.

MD7PL-PFF

MD7PL-PFG

MD7PL-NFF

MD7PL-NFG

Max. continuous operating voltage (Uc)

Line to Line

-30V

+30V

Line to Earth

±160V

Line to SHLD

±160V

SHLD to Earth

±160V

short

±160V

short

Voltage protection level (Up)

Line to Line

-50V

+50V

@6kV (1.2 / 50 µs)

Ling to Earth

±800V

Line to SHLD

±1200V

±800V

±1200V

±800V

SHLD to Earth

±800V

short

±800V

short

Leakage current @Uc

Line to Line

≤5µA

Other sections

≤5µA

Response time

Line to Line

≤4 nsec.

Other sections

≤20 nsec.

Max. discharge current (Imax)

20kA (8 / 20 µs), 1.0kA (10 / 350 µs)

Nominal current (I

N

)

100mA

Internal series resistance

11Ω ±10% per line