EM-8064  Rev.2  P. 1 / 4

INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR

SELF-SYNCH

 (ultra-slim)

MODEL

MD7JS

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, please 
contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the surge 
voltages.
However, M-RESTER may not be effective against certain 
extremely high voltages caused by a direct or almost direct 
hit by lightning.
M-RESTER must be installed according to this installation 
/ instruction manual.

GENERAL

 

FUNCTION & FEATURES

• 

High discharge current capacity 20 kA (8 / 20 µs), 1 kA 
(10 / 350 µs)

• 

Ultra-thin 7-mm-wide module can be mounted in high 
density

• 

Excellent protection employing multi-stage SPD circuits

• 

DIN rail mounting and grounding

• 

Shield terminal provided

• 

Protects self-synch transmitters and converters

 

SPECIFICATIONS

LINE TO LINE

LINE TO EARTH

Max. continuous
operating voltage (Uc)

±130V

±160V

Voltage protection level
(Up) @6kV (1.2 / 50 µs)

±450V

±800V

Leakage current @Uc

≤20µA

≤5µA

Response time

≤4 nsec.

≤20 nsec.

Max. discharge current 
(Imax)

20kA (8 / 20 µs)

1kA (10 / 350 µs)

Nominal current (I

N

)

500mA

Internal series resistance

2Ω ±10% per line

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

Operating temperature: -5 to +40°C (23 to 104°F)

• 

Operating humidity: 30 to 80% RH (non-condensing)

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -25 to +55°C 
(-13 to +131°F) with relative humidity within 30 to 90% 
RH in order to ensure adequate life span and operation.

• 

This unit needs a DIN rail as earth grounding bar.  Ox-
ide coating of an aluminium rail may lower the electric 
conductivity between this module and the ground.  Use a 
steel or copper rail.

 

DIELECTRIC STRENGTH TESTING

• 

The surge protector starts discharging when a voltage 
greater than 160V is applied between lines and earth.  
Remove the grounding wire before conducting a test.  Be 
sure to return the wire after the test.

 

AND ....

• 

We recommend that you keep spare surge protectors so 
that you can replace them when necessary.

• 

Lightning surge can enter not only through signal lines 
but also through power supply lines.  We recommend that 
you also use the Lightning Surge Protector for Power 
Lines for adequate protection.