background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8171  Rev.8  P. 1 / 3

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Lightning surge protector (body + base socket) .................(1)
Fuse (spare parts) ...............................................................(2)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Designed specifically for AC power supplies up to 2 amps
• No degradation of normal (50/60 Hz) line frequency
• Power indicator lamp provided

 

SPECIFICATIONS

BETWEEN LINES

LINE TO GND

MA-100

MA-200

Discharge voltage
(peak voltage)

190V min. 410V min.

410V min.

Max. surge voltage*
(peak voltage)

350V max. 700V max.

700V max.

Leakage current

≤ 1mA

@150V DC

≤ 1mA

@300V DC

≤ 1 mA

@300V DC

Rated line voltage

100V AC
110V AC
120V AC

200V AC
220V AC
240V AC

----

Response time

≤ 0.1 µsec.

Discharge current

1000A (8 / 20 µsec.)

Max. load current

2A

Voltage drop

≤ 2V (50/60 Hz)

*  The maximum voltage that could pass through the surge 

protector.  Protected equipment must be able to withstand 
this voltage for a very short time period.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for use in Pollution Degree 2 

and Installation Category II (transient voltage 2500V for 
MA-200 and 1500V for MA-100) environments.

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the surge protector inside proper housing with 
sufficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 
impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

DIELECTRIC STRENGTH TEST

• Unplug the body from the base socket before conducting a 

dielectric strength test.  If the test is performed with the 
body, the surge protector will start discharging at the de-
scribed discharge voltage, resulting as insulation failure.  
Be sure to plug the body back into the socket and secure 
it with the clamps after the testing is complete.

 

AND ....

• We recommend that you keep spare surge protectors so 

that you can replace them when necessary.

• Lightning surge can enter not only through power supply 

lines but also through signal lines.  We recommend that 
you also use the surge protectors for signal line for suffi-
cient protection.

LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY

(2A)

MODEL

MA-100

MA-200