31
M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.2.2 MAXIMUM RANGE, MINIMUM sPAN AND DEFAULT VALUE OF INPUT
The maximum range, minimum span and default value of the input are shown in the following tables. The default value
means initial 0% and 100% input when the DIP switch setting is changed.
10.2.2.1 DC current input
MAXIMUM RANGE
MINIMUM SPAN
DEFAULT VALUE
0 to 20 mA DC
1 mA
4 to 20 mA DC
10.2.2.2 DC voltage input (mV)
MAXIMUM RANGE
MINIMUM SPAN
DEFAULT VALUE
-1000 to +1000 mV DC
4 mV
0 to 1000 mV DC
10.2.2.3 DC voltage input (V)
MAXIMUM RANGE
MINIMUM SPAN
DEFAULT VALUE
-10 to +10 V DC
1 V
1 to 5 V DC
10.2.2.4 Thermocouple input
Minimum span: 20°C (36°F)
Default value: same as conformance range in °C
THERMOCOUPLE
°C
°F
MAXIMUM RANGE
CONFORMANCE RANGE MAXIMUM RANGE
CONFORMANCE RANGE
(PR)
0 to 1760
0 to 1760
32 to 3200
32 to 3200
K (CA)
-270 to +1370
-150 to +1370
-454 to +2498
-238 to +2498
E (CRC)
-270 to +1000
-170 to +1000
-454 to +1832
-274 to +1832
J (IC)
-210 to +1200
-180 to +1200
-346 to +2192
-292 to +2192
T (CC)
-270 to +400
-170 to +400
-454 to +752
-274 to +752
B (RH)
100 to 1820
400 to 1760
212 to 3308
752 to 3200
R
-50 to +1760
200 to 1760
-58 to +3200
392 to 3200
S
-50 to +1760
0 to 1760
-58 to +3200
32 to 3200
C (WRe 5-26)
0 to 2315
0 to 2315
32 to 4199
32 to 4199
N
-270 to +1300
-130 to +1300
-454 to +2372
-202 to +2372
U
-200 to +600
-200 to +600
-328 to +1112
-328 to +1112
L
-200 to +900
-200 to +900
-328 to +1652
-328 to +1652
P (Platinel II)
0 to 1395
0 to 1395
32 to 2543
32 to 2543