EM-2663-A  Rev.3  P. 1 / 7

INSTRUCTION MANUAL

POTENTIOMETER TRANSMITTER

(field- and PC-configurable)

MODEL

M3LM

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner ...............................................................(1)
I/O range and tag name label sheet ...................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.  For detailed information, 
refer to the operating manual (EM-2663-B).
The M3LM with Option A is programmable using the PC 
configurator software.  For detailed information on the PC 
configuration, refer to the M3CFG instruction manual.  The 
M3CFG PC Configurator Software and operating manual 
are downloadable at M-System’s web site: http://www.m-
system.co.jp.

POINTS OF CAUTION

 

CONFORMITY WITH UL

• This equipment is suitable for use in a Pollution Degree 

2 environment.

• This equipment is to be used with the maximum operat-

ing voltage 30Vrms and 42.4Vpeak or 60V DC.

• The equipment must be mounted inside a suitable fire 

enclosure.

• Operating temperature: -25 to +55°C (-13 to +131°F)

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• Insert noise filters for the power source, input and output 

connected to the unit.  COSEL Model NAC-04-472, TDK 
Model ZCAT 3035-1330 or equivalent is recommended.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    10 – 32V DC rating: 9 – 36V, approx. 3W

 

GENERAL PRECAUTION

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -25 to +65°C 

(-13 to +149°F) with relative humidity within 0 to 95% 
RH in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for M3LM

Page 1: ...472 TDK Model ZCAT 3035 1330 or equivalent is recommended The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this...

Page 2: ...where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from th...

Page 3: ...NECTION DIAGRAM CONFIGURATOR JACK 7 8 11 12 OUTPUT POWER 4 5 1 3 2 1 POTENTIOMETER max min WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinnin...

Page 4: ...type and ranges are listed in Table 7 and 8 DIP SW CONFIGURATION MODE Turn the SW2 8 OFF to enable the DIP SW Field Configuration mode as shown in Table 1 See Table 3 to configure the input and Table...

Page 5: ...o 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LM x A or the green LED turns on model M3LM x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1...

Page 6: ...nk RUN MODE LD2 LD3 A G RUN MODE LD2 LD3 G R LD1 LD2 LD3 LD1 LD2 LD3 0 INPUT CONFIGURED 100 INPUT CONFIGURED INPUT RANGING MODE LD1 OUTPUT RANGING MODE LD2 LD3 LD1 LD2 LD3 0 OUTPUT CONFIGURED 100 OUTP...

Page 7: ...ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 6 Burnout in PC Configuration Mode Op...