LION microPLC
▪
Maintenance – Software
50
2. The content of this file must look like this:
ReadStart = 0x08080000
ReadLength = 0x00080000
ReadFile = Name.bin
3. These files must then be uploaded to the SD card via FTP
(
see also chapter 12.1.1 Procedure via FTP upload on page 43
4. After the file is on the microSD card, the device must be restarted. When re-
booting, the application with the „
Name.bin
“ will be copied to the SD card.
5. The application file „
Name.bin
“ can only then be copied from the SD card via
FTP.
12.3.2
Write application
1. Create the
bootloader configuration file
"
BTLDRCFG.ini
". For this a txt file is
created, which must be named "
BTLDRCFG"
. Then the extension must b
changed from
.txt
to
.ini
.
The
ReadStart
and the
ReadLength
must not be changed, because the content
of the application is stored there. The identifier
ReadFile
specifies the name on
the SD card.
The name may be max. 8 ASCII characters long. Numbers, letters and
selected special characters are possible.
See also allowable characters in
chapter 12.3.1 Read application on page 49
There should be no firmware file on the SD card.
The configuration file should be deleted, otherwise the application is
always written to the SD card with every restart.
With bootloader version <1.06 the PLC is no longer reachable if not
allowed special characters are used for the BIN file of the application.
Only at version 1.06 the PLC boots anyway and can be reached via Multiprog
and FTP.
Allowed characters
^
-
_
'
#
()
!
$
%