Control
Selection
21
© Lutz-Jesco GmbH 2015
Subject to technical changes.
150527
BA-70200-02-V01
Polymer preparing and dosing station EASYPURE Powder and Liquid
Operating instructions
AGITATOR 2
By pressing the „I“ key, the agitator is turned on. This function is
independent of the level of the container. The motor icon changes to
switching control, the color green / red
By pressing the red button „0“ the agitator is switched off again.
With the BACK button to return to the previous menu item. If this button
does not turn on due to a malfunction of the Touchpanel, can be
performed by pressing F4 also a back step.
With the key CLOCK the bottom left or the F1 key, the external alarm
signal can be suppressed for 2 minutes (siren, flashing light, etc.).
Fig. 13: AGITATOR 2
DRY FEEDER
By pressing the „I“ button the dry feeder and the mouthpiece heating is
on for max. 2 minutes continuous operation. This function is independent
of the level of the tank and the water supply. The engine symbol and the
parts of the dry material changes to control the color to green, the „I“
button (On) is to switch to „0“ (Off). Press the button % X to change the
Concentration – Save with “ENTER” key. A change in concentration
during the operation is possible at any time.
The alarm is signaling the Suspensomat Error and triggers when a
malfunction.
By pressing the button „0“ the function is switched off and it can be
switched on again manually. Leaving the picture with the BACK button
causes a shutdown of the dry feeder. If the BACK button does not turn on
due to a malfunction of the panel, can be performed by pressing F4 also a
back step.
With the key CLOCK the bottom left or the F1 key, the external alarm
signal can be suppressed for 2 minutes (siren, flashing light, etc.).
Fig. 14: DRY FEEDER
SOLENOID VALVE
By pressing the “I” key the solenoid valve is switched on for max. 2
minutes. This function depends on the level of the container. If the Max.
Level is reached, turning on the solenoid valve is not possible. Valve
symbol changes to control the color to green. The alarm of the flowmeter
Min. is inactive.
By pressing the button „0“ the function is switched off and it can be
switched on again manually.
Leaving the picture with the BACK button causes a shutdown of the
solenoid valve. If the BACK button does not turn on due to a malfunction of
the Touchpanel, can be performed by pressing F4 also a back step.
With the key CLOCK the bottom left or the F1 key, the external alarm
signal can be suppressed for 2 minutes (siren, flashing light, etc.).
Fig. 15: SOLENOID VALVE
Summary of Contents for EASYPURE 1000