030-1307
6
Mount and align control. Install wallplate (purchased separately).
7
Turn power on.
5
Wiring the control.
• Connect the
green
dimmer wire to
the bare copper or green ground
wire in the wallbox, if present (see
Important Note 5).
• Using a wire connector, connect
the
black
dimmer wire to either
of the wires removed from the
switch.
• Using a wire connector, connect
the
red
dimmer wire to the
remaining wire removed from the
switch.
• Using a wire connector, cap off
the
red/white
dimmer wire. This
wire is not used in a single pole
circuit.
• Connect the
green
dimmer wire to
the bare copper or green ground
wire in the wallbox, if present
(see Important Note 5).
• Using a wire connector, connect
the
black
dimmer wire to the
wire removed from the different-
colored screw on the switch
(marked or tagged wire). Remove
tag from wire.
• Using a wire connector, connect
the
red
dimmer wire to either
of the remaining wires removed
from the switch.
• Using a wire connector, connect
the
red/white
dimmer wire to the
remaining wire removed from
the switch.
Installation
For installations involving more than one control in a wallbox, refer to Multi-Unit
Installations before beginning.
1
Turn power off at circuit breaker or remove fuse.
2
Remove wallplate. Pull switch from wall.
3
Identify type of switch:
4
Disconnecting switch wires.
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Made and printed in U.S.A.
5/10 P/N 030-1307 Rev. A
Single Pole / 3-Way
Tu-Wire
®
Fluorescent Controls
Rated at 120 V 60 Hz
5 A maximum total current
Important Notes
Please read before installing.
1.
CAUTION:
To avoid overheating and possible damage to other equipment,
do not use to control receptacles, motor-operated or transformer-supplied
appliances.
2. Use only to control Lutron Tu-Wire
®
fluorescent dimming ballasts.
3. For proper dimming performance lamps must be operated at full intensity
for 100 hours prior to dimming.
4. Only one control can be used in a 3-way circuit.
5. When no “grounding means” exist within the wallbox then the NEC
®
2008, Article 404.9 allows a dimmer without a grounding connection to be
installed as a replacement, as long as a plastic, noncombustible wallplate
is used. For this type of installation, cap or remove the green ground wire
on the dimmer and use an appropriate wallplate such as Fassada
®
series
wallplates by
Lutron
.
6. For new installations, wire a test switch before installing the control.
7. Control may feel warm to the touch during normal operation.
8. Install in accordance with all national and local electrical codes.
Multi-Unit Installations
When combining controls in a wallbox, remove all inner side sections prior
to wiring (see below). Use pliers to bend side section up and down until it
breaks off. Repeat for each side section to be removed. Reduction of control
capacity is required. Refer to chart below for maximum control capacity.
Black
Red
Ground
Red/White
Green
OR
Turn screws to
loosen
Ground
(Bare Copper or
Green Wire)
Different-Colored Screw
(Common)
Tag
3-WAY:
Insulated wires connected to three screws.
MARK or TAG
insulated wire connected to
different-colored screw or screw labeled
COMMON.
Ground
(Bare Copper or
Green WIre)
SINGLE POLE:
Insulated wires connected to two same
color screws.
OR
Backwired:
Insert screwdriver. Pull out wire.
Terminal Screws:
Turn screw to loosen
No sides
1 side
2 sides
removed
removed
removed
Maximum Current
5 A
4 A
3.3 A
To determine total ballast load, add the line current found on the ballast label
for all ballasts in the circuit. This will indicate the total load for the control.
When making wire connections, twist and
trim wires to the proper length as indicated:
Note:
Wire connectors provided are
suitable for
copper wire only
. For
aluminum wire, consult an electrician. Use
connectors to join one 14 AWG (1.5 mm²)
supply wire with one 16 AWG or 18 AWG
(1.0 mm² or 0.75 mm²) control wire.
Twist wire
connector tight.
Be sure no
bare wire is
exposed.
3/8 in
Twist wires
and trim.
Lutron
®
Tu-Wire
®
ballast
Live
Black
Red/White
Red
Green
Neutral
Load
3-Way Switch
120 V~
60 Hz
Ground
Lutron
®
Tu-Wire
®
ballast
Live
Load
Neutral
Black
Red
Red/White
Green
Ground
120 V~
60 Hz
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For
warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
THIS WARRANTY IS IN LIEU OF ALL OTHER ExPRESS WARRANTIES, AND THE IMPLIED WARRANTY OF MERCHANTABILITY IS LIMITED
TO ONE YEAR FROM PURCHASE. THIS WARRANTY DOES NOT COVER THE COST OF INSTALLATION, REMOVAL OR REINSTALLATION,
OR DAMAGE RESULTING FROM MISUSE, ABUSE, OR DAMAGE FROM IMPROPER WIRING OR INSTALLATION. THIS WARRANTY DOES
NOT COVER INCIDENTAL OR CONSEqUENTIAL DAMAGES. LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN
CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER ExCEED THE PURCHASE
PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow
the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above
limitations may not apply to you.
Lutron, Tu-Wire, and Fassada are registered trademarks of Lutron Electronics Co., Inc. © 2010 Lutron Electronics Co., Inc.
• Easy-to-follow
Instructions
• Instructions
faciles à suivre
• Easy-to-follow
Instructions
• Instructions
f
aciles à suivre
Remove All Inner
Side Sections
(shaded)
Do Not Remove
Outer Side Sections
Start screws
Align control and
tighten screws
Note:
For proper dimming performance lamps must be
operated at full intensity for 100 hours prior to dimming.
ON
OFF
ON
OFF
ON
OFF
WARNING:
Shock Hazard. May result
in serious injury or death.
Turn off
power at circuit breaker before
installing the unit.
SINGLE POLE circuit
Black
Red
Green
Tag
Ground
Red/White
3-WAY circuit:
English
Important Wiring Information
Models:
DVFTU-5A3P
DVSCFTU-5A3P
SFTU-5A3P
Technical Assistance
If you have questions concerning the installation or operation of this
product, call the
Lutron Technical Support Center
. Please provide
exact model number when calling.
U.S.A. and Canada (24 hrs/7days)
1.800.523.9466
México
+1.888.235.2910
Other countries 8am – 8pm ET
+1.610.282.3800
Fax
+1.610.282.6311
http://www.lutron.com
Lutron Technical Support Center 1.800.523.9466 24 hrs / 7 days www.lutron.com