background image

seeTouch

®

 guestroom solutions

Installation Guide

Please Read

IMPORTANT:

• Lighting controls must be installed by a qualified electrician in accordance with all applicable regulations. 

 

WARNING: Shock Hazard. 

May result in death or serious injury.

 

DO NOT WIRE LIVE! Interrupt 

power via circuit breaker before wiring and servicing. 

• Always turn off circuit breaker/MCB or remove main fuse from power line before doing any work.
• To reduce the risk of overheating and possible damage to other equipment, the module must be mounted 

as shown. Failure to provide adequate space for cooling may result in overheating and void the warranty.

• Module hums slightly during operation and the internal relay clicks when the circuit is turned on and off. 

Choose an installation location where these sounds are acceptable.

• Lighting controls are designed for commercial indoor use only.
• This control uses PELV wiring methods. Check with your local electrical inspector for compliance with 

national and local codes and wiring practices.

230 V

  50/60 Hz   8,75 A   (40 – 350 W per zone)

24 V

    200 mA   (Panels with a power supply only)

Summary of Contents for seeTouch guestroom solutions

Page 1: ...eating and possible damage to other equipment the module must be mounted as shown Failure to provide adequate space for cooling may result in overheating and void the warranty Module hums slightly dur...

Page 2: ...2 seeTouch guestroom solutions...

Page 3: ...sing power interfaces Provides individual control of light sources Includes built in astronomic timeclock Includes one contact closure input and 24 V power for occupant sensors or other building manag...

Page 4: ...and local codes as necessary Mount panel so line mains voltage wiring is at least 1 8 m 6 ft from sound or electronic equipment and wiring Lutron recommends using 6 mm 0 25 in mounting bolts Allow 32...

Page 5: ...ntrolled with an appropriate interface Not all zones need to be connected however connected zones must have a load of at least 40 W No zone may be loaded with more than 350 W Maximum load capacity for...

Page 6: ...pply see model descriptions for details 1 2 3 4 1 2 3 4 Panel 1 Non RF Panel with power supply Panels with power supplies can power up to 10 wallstations and cannot have terminal 2 tied to other panel...

Page 7: ...insulation from both twisted pairs in the wallbox Two 1 0 mm2 18 AWG conductors for common terminal 1 and 24 V terminal 2 These will not fit in terminals Connect as shown One shielded twisted pair 0...

Page 8: ...on type current probe The current probe should measure no more than 8 75 A 3 Turn loads ON for at least ten minutes If circuit breaker trips turn power OFF then locate and correct miswire or overload...

Page 9: ...ment and cables not provided Network Connections DIP Switches LED 1 Power LED 2 3 Unused LED 4 RS232 Link Tx LED 5 RS232 Link Rx LED 6 Data Link Tx LED 7 Data Link Rx Data Link to control units proces...

Page 10: ...CO 4 NC CCO 4 NO CCO 5 NC CCO 5 NO 5 COM CCI 1 CCI 2 CCI 3 CCI 4 CCI 5 COM Contact Closure Outputs Contact Closure Inputs 1 2 3 4 5 6 7 Program button 2 24 V Contact Closure Ratings Five Input Termina...

Page 11: ...VE IS SPECIFICALLY INCLUDED HEREIN OR IN STANDARD PRINTED MATERIALS PROVIDED BY LUTRON IT DOES NOT FORM A PART OF THE BASIS OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE ENFORC...

Page 12: ...1536 Hong Kong 800 901 849 Indonesia 001 803 011 3994 Japan 81 3 5575 8411 Macau 0800 401 Singapore 800 120 4491 Taiwan 00 801 137 737 Thailand 001 800 120 665853 Other countries 65 6220 4666 Contact...

Page 13: ...obrecalentamietnto y posibles da os a los equipos el m dulo deber montarse como se muestra Si no se dispone del espacio adecuado para el enfriamiento podr a producirse un sobrecalentamiento y quedar a...

Page 14: ...e potencia Proporciona control individual de las fuentes de iluminaci n Incluye reloj astron mico integrado Incluye una entrada de cierre de contacto y alimentaci n de 24 V para sensores de presencia...

Page 15: ...acuerdo al peso y a las normas locales seg n sea necesario Instale el cuadro de modo que la alimentaci n del cuadro quede alejada un m nimo de 1 8 m de otros equipos electr nicos o de audio y su cable...

Page 16: ...seeTouch MCB PELV 230 V 50 60 Hz 8 75 A 40 350 W 24 V 200 mA...

Page 17: ...seeTouch 3 seeTouch 24 V Lutron QS 3 4 5 6 7 8 9 10 11 12...

Page 18: ...4 seeTouch 0 40 C 1 8 6 32 63 8 kg 337 22 286 80 8 235 235 191 25 337 74 86 mm PELV PELV...

Page 19: ...seeTouch PELV 230 50 60 8 75 A 40 350 24 200...

Page 20: ...seeTouch 3 seeTouch 24 QS Lutron 3 4 5 6 7 8 Ethernet 9 10 11 12...

Page 21: ...4 seeTouch 0 40 C 1 8 Lutron 6 32 63 8 337 22 286 80 8 235 235 191 25 337 74 86 PELV PELV...

Reviews: