background image

Troubleshooting 

*

 

www.lutron.com

CCO-
controlled 
device does 
not respond 
to Wireless 
Transmitter(s)

•  Ensure breaker to the PowPak

®

 CCO Module is on.

•  Ensure the CCO-controlled device has been 

properly wired to the PowPak

®

 CCO Module.

•  Ensure Wireless Transmitter is properly associated 

to PowPak

®

 CCO Module.

•  Ensure Wireless Transmitter’s battery is installed 

correctly.

Wireless 
Transmitter(s) 
cannot be 
associated to 
PowPak

®

 CCO 

Module

•  The maximum number of Wireless Transmitters 

have been associated to the PowPak

®

 CCO 

Module. To remove a previously set up Wireless 
Transmitter, tap the button used for association on 
the Wireless Transmitter three times, on the third 
tap hold for three seconds and then tap three more 
times.

Unaffected Mode

Unaffected Mode allows a system with an Occupancy Sensor 
associated to multiple CCO Modules to be set up such that only 
selected loads turn on automatically. Other loads will require a manual 
turn-on with a Pico

®

 Remote Control. All loads will turn off automatically 

when the room is vacated. 

On a CCO Module, press and hold both the CCO Toggle and 
Advanced Operations (“ADV”) buttons for 6 seconds until the LED 
begins flashing quickly.

On the associated Occupancy Sensor, press and hold the “Test” 
button* for 6 seconds until the lens flashes.

Unaffected mode will be exited automatically. This CCO Module will 
now be unaffected by occupancy commands. Repeat procedure 
for any additional devices.

 

* If no “Test” button, hold “Lights On” button.

Reset Factory Defaults

 

 Note:

 In some instances it may be necessary to reset the PowPak

®

 

CCO Module back to factory default settings. 

Triple-tap the Advanced Operations (“ADV”) button on the CCO 
Module and hold until the LED begins to flash slowly.

Within 3 seconds of flashing, release and triple-tap the button again 
and the LED will flash rapidly indicating that the unit has been reset 
to factory defaults.

 Note: 

Any associations or programming previously set up with the 

unit will be lost and will need to be re-programmed.

Test

Link

Test

Link

Cal.

Test

Link

Cal.

CCO Information

  This product features a single contact closure output with both 

normally open (NO) and normally closed (NC) dry contacts. 

  The CCO incorporates maintained output behavior only.

  The CCO is rated to switch resistive loads at 

voltages up to 24 V only. To properly control 
inductive load types such as relays, solenoids, 
or motors, refer to Application Note #434.

Switching 
Voltage

0-24 V

-

0-24 V

~

Resistive 
Load

 

1.0 A
0.5 A

R

Transmitting Device

Transmitted Command

CCO Default Action

Pico

®

  

Remote Control

On

NO = Close,  NC = Open

Off

NO = Open,  NC = Close

Raise

No Action

Lower

No Action

Preset

NO = Close,  NC = Open

Radio Powr Savr

TM

 

Occupancy Sensor

Occupied

NO = Close,  NC = Open

Unoccupied

NO = Open,  NC = Close

Radio Powr Savr

TM

 

Vacancy Sensor

Occupied

No Action

Unoccupied

NO = Open,  NC = Close

Radio Powr Savr

TM

 

Daylight Sensor

Ambient light below target 
level

NO = Close,  NC = Open

Ambient light above target 
level

NO = Open,  NC = Close

Part of the Energi TriPak

®

 Family

PowPak

®

 | Installation

CCO Module

English

Lutron Electronics Co., Inc. | 7200 Suter Road 
Coopersburg, PA 18036-1299, U.S.A.

041505 
Rev. A 
09/2015

Need Help? www.lutron.com or call the Lutron Technical Support Center, at 1.800.523.9466

For each system ensure you have:

At least one PowPak

®

 CCO Module.

At least one Wireless Transmitter. 

Required Components

Start Here

1

When installing a PowPak

R

 CCO Module,  

use the supplied conduit nut and wire the module 
as shown.

Install PowPak

R

 Relay Module

Associate Wireless Transmitters to PowPak

R

 CCO Module 

*

Hold the CCO Toggle  
button on the PowPak

®

  

CCO Module for 6 seconds  
to enter association mode.

Before beginning this step, make sure that there are no other PowPak

®

 modules being set up within the same building. It is possible that Wireless Transmitters 

from other systems can be incorrectly associated to this system.

2

3

Permanently Install  
Wireless Transmitters

Note:

 Please consult individual component 

installation guides for information.

Shock Hazard. May result in serious injury or death.  

Turn off power at circuit breaker before installing the unit.

WARNING

Radio Powr Savr

TM

 Occupancy  

Sensor (10 maximum)

PowPak

®

 CCO Module

Load  
Status  
LED

CCO Toggle

Advanced 
Operations

Contact 
Closure 
Output 
(CCO)
(Class 2)

Suggested Installation Location:

Install in center of room.  

This ensures proper RF coverage of area.

Hold the indicated button on a Wireless Transmitter for  
6 seconds to associate the device.* 
Repeat for any additional Wireless Transmitters.

Hold the CCO Toggle button on the PowPak

®

  

CCO Module for 6 seconds to save association(s).

* If no 

g

 button, hold “Lights Off” button.

Note:

 The CCO will open and 

close once after each step to 
confirm successful completion.

Test

Link

Daylight Sensor setup 

*

Calibration

Turn lights in room on using the CCO 
Toggle button on the PowPak

®

 CCO 

Module or an associated Pico

®

Press & hold “Cal.” on the associated 
Daylight Sensor for 6 seconds.

Exit room for 5 minutes to allow 
calibration to be completed.

           

Note:

 When calibration has completed, all 

lights will flash and the system will begin 
daylighting.

If it is desired to have multiple zones of  
lights turn on at different daylight levels  
(using multiple CCO Modules with one  
Daylight Sensor) follow the Tuning 
procedure described in the Daylight Sensor 
(LRF2-DCRB) installation instructions.  

 

Use the CCO Toggle button in place of the  
Dimmer/Switch tap button referenced in  
the document.

Tuning (Optional)

4

Radio Powr Savr

TM

 

Daylight Sensor
(1 maximum)

Pico

®

 Remote 

Control  
(10 maximum)

   Important Notes: 

Please read before installing.

•  

For installation by a qualified electrician in accordance with all local and national 
electrical codes. 

• Note:

 Use copper conductors only.

• 

Check to see that the device type and rating is suitable for the application.

• DO 

NOT

 install if product has any visible damage.

• 

 If moisture or condensation is evident, allow the product to dry completely before 
installation.

• 

Operate between 32 °F (0 °C) and 131 °F (55 °C).

• 

0% to 90% humidity, non-condensing.

• 

For indoor use only.

RMJS-CCO1-24-B 
URMJS-CCO1-24B

24 V

~

   45  mA     

24 V

-

 35 mA 

NEC

®

 CLASS 2

UL 2043 Plenum Rated

COM

(Common)

NO

(Normally Open)

NC

(Normally Closed)

Wire nut   

(2 Supplied)

Supply Voltage
24 V

~

 / 24  V

-

Note:

 CCO Module supply wires can be 

connected in any polarity.

Mounting screw

 

(2 Supplied)

Note:

 When wiring CCO output,  

use 20 AWG to 16 AWG  
(0.5 mm

2

 to 1.5 mm

2

) solid or stranded wire.

To CCO-controlled device

Note: 

PowPak

®

 CCO Module may also be 

mounted on or inside a junction box.

If installing unit inside a junction box please  
see Application Note #423.

For more information:

  

www.lutron.com/powpakcco

Radio Powr Savr

TM 

Occupancy Sensor  

30 ft (9 m)

Maximum

40 ft (12 m)

9 ft (10 m)

PowPak

®  

CCO Module 

Install in center of room to 

maximize RF coverage.

Pico

®

  

Remote 
Control

FCC / IC  Information:

This device complies with part 15 of the FCC Rules and Industry Canada licence-exempt RSS 
standard(s). Operation is subject to the following two conditions:

(1) This device may not cause interference, and

(2) This device must accept any interference, including interference that may cause undesired operation.

Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to 
operate this equipment.

NOTE: 

This equipment has been tested and found to comply with the limits for a Class B digital device, 

pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection 
against harmful interference in a residential installation. This equipment generates, uses and can radiate 
radio frequency energy and, if not installed and used in accordance with the instructions, may cause 
harmful interference to radio communications. However, there is no guarantee that interference will not 
occur in a particular installation. If this equipment does cause harmful interference to radio or television 
reception, which can be determined by turning the equipment off and on, the user is encouraged to try 
to correct the interference by one or more of the following measures:

• Reorient or relocate the receiving antenna.

• Increase the separation between the equipment and receiver.

•  Connect the equipment into an outlet on a circuit different from that to which the receiver is 

connected.

Note for Replacement:

RMxS and URMxS - the "S" model can replace the non-"S" model

*

   For set-up, programming, and troubleshooting with a Vive

TM

 

system, please refer to the installation instructions included 
with the Vive

TM

 hub or at www.lutron.com

All Wireless Transmitters must be installed within  
30 ft (9 m) of the PowPak

®

 CCO Module.

 

+

Limited Warranty

(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty 
service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.

This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This 
warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or damage from improper 
wiring or installation. This warranty does not cover incidental or consequential damages.

LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, 
SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.

This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the 
exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations 
may not apply to you.

Lutron, Energi TriPak, Pico, and PowPak are registered trademarks and Radio Powr Savr and Vive are trademarks of  
Lutron Electronics Co., Inc.  
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts. 

©2015 Lutron Electronics Co., Inc.

Reviews: