background image

Maestro

®

Sensor

369741a 5  11.15.12

®

S P E C I F I C AT I O N   S U B M I T TA L

Page

Job Name:

Job Number:

Model Numbers:

Switch with Occupancy/ Vacancy Sensor

5 ft

 

(1.5 m)

10 ft

 

(3 m)

15 ft

 

(4.5 m)

20 ft

 

(6 m)

25 ft

 

(7.5 m)

30 ft

 

(9 m)

Horizontal Beam Diagram

5 ft

 

(1.5 m)

5 ft

 

(1.5 m)

0

10 ft

 

(3 m)

10 ft

 

(3 m)

15 ft

 

(4.5 m)

15 ft

 

(4.5 m)

20 ft

 

(6 m)

20 ft

 

(6 m)

25 ft

 

(7.5 m)

25 ft

 

(7.5 m)

30 ft

 

(9 m)

30 ft

 

(9 m)

Vertical Beam Diagram

4 ft

 

(1.2 m)

0

0

10 ft

 

(3 m)

15 ft

 

(4.5 m)

20 ft

 

(6 m)

25 ft

 

(7.5 m)

30 ft

 

(9 m)

NEMA WD7 Coverage

5 ft

 

(1.5 m)

5 ft

 

(1.5 m)

0

10 ft

 

(3 m)

10 ft

 

(3 m)

15 ft

 

(4.5 m)

15 ft

 

(4.5 m)

5 ft

 

(1.5 m)

Major motion coverage: 900 ft

2

 (81 m

2

)

Minor motion coverage: 400 ft

2

 (36 m

2

)

Occupancy Sensing Switch Placement and Operation

•   The ability of the Occupancy sensing switch to detect motion requires line-of-sight of room occupants. The 

Occupancy sensing switch must have an unobstructed view of the room.

•   Hot objects and moving air currents can affect the performance of the Occupancy sensing switch.
•   The performance of the Occupancy sensing switch depends on a temperature differential between the ambient 

room temperature and that of room occupants. Warmer rooms may reduce the ability of the Occupancy sensing 

switch to detect occupants.

Definitions

Major motion:

 movement of a person entering or passing through an area.

Minor motion:

 movement of a person occupying an area and engaging in small activities (e.g., reaching for a 

telephone, turning the pages of a book, opening a file folder, picking up a coffee cup).

5