Dual Technology Switch with Occupancy Sensor

369773b   3   12.19.13

Maestro

®

Sensor

Custom Settings

Default settings shown in bold

 

 - Timeout

•  30 min

•  15 min

•  5 min
•  1 min

 

Mode

 - Sensor Modes

  Lights automatically turn off in all sensor modes
• 

Occ -Occupancy mode (No ALD) 

1,2,3

•  Lrn - Occupancy with learning ALD mode
•  Fixd - Occupancy with fixed ALD mode
•  Vac - Vacancy mode (No ALD) 

2,3

1   MS-B102-XX default is Occ

2   MS-B102-V-XX is locked as Vac

3   MS-B202-XX defaults are:  Circuit 1 - Occ, Circuit 2 - Vac

 
 

 - 

Ultrasonic Sensitivity

• High
• 

Med

• Low
• Off

 

 - 

Passive Infrared Sensitivity

• High

• Med
• Low
• Min

Additional Settings

  Fixed ALD Light Level

• Hi
• Med

•  Low *

• Min

*  

“Low” is the default setting for any sensor that is  

set by the user to: Occupancy with fixed ALD mode

 

Off-While-Occupied

• Enabled

• Disabled
 

 

Walk-Thru Mode

• Enabled

• Disabled

Custom Settings - Details

Ambient Light Detection (ALD) mode

Lights turn on only when natural light in the room is 
below the set threshold.
–  

Learning:

 The Ambient light threshold adjusts to 

the user’s preference via manual interaction with 
the sensor switch.

–  

Fixed: 

Choose a fixed ALD light level from four 

pre-set options:  
High, Medium, Low, and Minimum

Manual Off-While-Occupied Options

ENABLED

 (default setting)

–   When the sensor switch is manually turned off, 

the sensor switch will not turn the lights back on 
automatically while the room is occupied.

–   Once the room is vacated, the Auto-on feature 

returns to normal operation after the timeout 
period has expired.

–   This may be the preference in conference rooms 

or classrooms while viewing presentations. This 
feature requires motions to keep the lights off.

DISABLED

–   When the sensor switch is manually turned off, 

the Auto-on feature will return to normal operation 
after 25 seconds.

–   This may be the preference in a restroom if the 

user always wants the lights to turn on upon 
entering and the lights to turn off when the room 
is vacant.

Walk-Thru Mode

ENABLED 

1

–  

If motion is 

not

 detected within 3 minutes after initial 

occupancy, the lights will turn off after 3 minutes, 
instead of the current timeout.

–  

This setting may be the preference in commercial 
applications where personnel may briefly trigger 
sensors during non-working hours.

DISABLED

 (default setting)

–  

When motion is detected, the lights will ALWAYS remain 
on for the entire timeout duration, regardless of the 
duration of occupancy detection.

1

 

 1 minute timeout would be overridden if walk-thru mode is  

also ENABLED

Summary of Contents for Maestro MS-B102 Series

Page 1: ...r field of view Tamper resistant PIR lens Up to 900 ft2 81 m2 major motion coverage and 400 ft2 36 m2 minor motion coverage Two Ambient Light Detect ALD options Learning ALD Mode Uses adaptive algorit...

Page 2: ...rs operate by triggering initial occupancy using PIR technology and maintain occupancy using both ultrasonic and PIR technology Advanced Features Switching Adaptive zero cross switching maximizes rela...

Page 3: ...light level from four pre set options High Medium Low and Minimum Manual Off While Occupied Options ENABLED default setting When the sensor switch is manually turned off the sensor switch will not tu...

Page 4: ...ghting1 2 0 A 6 A1 2 Yes Fan2 4 4 A 1 6 HP 2 120 277 V Lighting1 6 A 1 MS B202 120 V Lighting1 2 0 A 6 A per circuit 1 2 Yes Fan2 4 4 A 1 6 HP per circuit2 120 277 V Lighting1 6 A per circuit1 1 Senso...

Page 5: ...r passing through an area Minor motion movement of a person occupying an area and engaging in small activities e g reaching for a telephone turning the pages of a book opening a file folder picking up...

Page 6: ...ng Wallbox Sensor switch Wallplate Adapter Wallplate sold separately Mounting screws Adapter mounting screws Operation m 30 15 5 1 Occ Lrn Fixd Vac Mode Hi Med Low Off Hi Med Low Min PIR PIR Sensor le...

Page 7: ...d Low Off Hi Med Low Min PIR PIR Sensor lens Top Tap button Controls Circuit 1 tap on off Ultrasonic Sensitivity Button PIR Sensitivity Button Sensor LED behind lens Pulses during Test mode Bottom Tap...

Page 8: ...Neutral Black Black Load Green White Blue Line Hot 120 277V 50 60Hz m 30 15 5 1 Hi Med Low Off Occ Lrn Fixd Vac Mode Hi Med Low Min PIR MS B102 Black Blue White Ground Black Blue Green Ground 120 277V...

Page 9: ...nd wire from the wallbox is connected to the green ground screw of the mechanical switch 2 Tag circuit Common Your 3 way mechanical switch should have three screw terminals two of the same color and o...

Page 10: ...tral Black Black Load 1 Load 2 Green Black Orange White Blue Line Hot Line Hot 120 277V 50 60Hz Ground Black Orange m 30 15 5 1 Occ LRN Fixd Vac Mode Hi Med Low Off Hi Med Low Min PIR m 30 15 5 1 Occ...

Page 11: ...2 NOTE Do not use Maestro Accessory switches with MS B202 3 Way Installation For retrofit 3 way installations the mechanical switch needs to be rewired as shown in the diagram below after wiring the D...

Page 12: ...2 12 19 13 Maestro Sensor How Loads Operate in 3 way with Dual Circuit Sensor Switch MS B202 Initial Load State After flipping 3 way mechanical switch Circuit 1 Circuit 2 Circuit 1 Circuit 2 When All...

Page 13: ...colors perfectly Color chip keychains are available for more precise color matching Gloss Finishes DG CK 1 Satin Finishes SC CK 1 Satin Finishes Taupe TP Turquoise TQ Plum PL Merlot MR Terracotta TC S...