background image

Limelight by Lutron OEM Integration Guide

5

Customer Assistance: 1.844.LUTRON1

(1.844.588.7661) 

4. LL-PIR-(L/M/H) Integration

The LL-INTMOUNT can be connected to an external Limelight by Lutron Passive Infrared sensor  
(LL-PIR-[L/M/H]) through the 4-pin connector shown below.

 

2.  Recommended plastic PIR lens assembly should be tightened to 4 in-lbs (0.45 N

m) to properly engage the 

internal seal.

3.  Visually inspect to verify plastic PIR lens assembly is seated properly, and not tilted relative to the fixture. Tilting 

could possibly imply cross-threading, which can lead to leaks and eventual failure of the product.

Good

Bad

Consistent spacing around the perimeter

Uneven spacing around the perimeter

1.   Connect LL-PIR to LL-INTMOUNT with cable assembly shown below (either end can connect to either  

LL-PIR or LL-INTMOUNT).

 

Ø1.18 

(Ø29.94)

Ø0.06 

(Ø1.69)

Ø0.99 

(Ø25.29)

1.08 

(27.47)

1.5 

(38.09)

 

LL-PIR External Sensor  

Connector

Summary of Contents for LL-INTMOUNT

Page 1: ...0 ft 4 9 to 9 m mounting height LL PIR H Limelight by Lutron PIR Sensor Assembly for 31 to 40 ft 9 5 to 12 m mounting height 3 LL INTMOUNT Integration Mechanical Integration Dimensions shown as in mm...

Page 2: ...tor slots For stranded wires press down on the button next to each connector slot to allow wire entry Releasing the button will cause the connector to grip the wire Wire Gauge 16 20 AWG 1 5 0 5 mm2 Th...

Page 3: ...le fixture for further RF testing If a sample is requested the required performance testing may take up to 3 weeks starting from when the sample is received by Lutron For best RF performance of the LL...

Page 4: ...erproof and should not be mounted in a location where it will receive direct contact with water It is however conformal coated and can withstand humid or moist conditions Regulatory Labelling Requirem...

Page 5: ...to properly engage the internal seal 3 Visually inspect to verify plastic PIR lens assembly is seated properly and not tilted relative to the fixture Tilting could possibly imply cross threading whic...

Page 6: ...it is commissioned correctly Luminaire Power Up Timing When the LL INTMOUNT powers up it cycles the luminaire through various states so the manufacturer can determine if the luminaire has been wired...

Page 7: ...bbean 1 800 523 9466 Mexico 1 888 235 2910 Central South America 1 610 282 6701 EUROPEAN HEADQUARTERS United Kingdom Lutron EA Ltd 6 Sovereign Close London E1W 3JF United Kingdom TEL 44 0 20 7702 0657...

Page 8: ...tage de 4 9 9 m 16 30 pi LL PIR H Ensemble de d tecteur PIR de Limelight par Lutron pour une hauteur de montage de 9 5 12 m 31 40 pi 3 Int gration de LL INTMOUNT Int gration m canique Dimensions repr...

Page 9: ...ton permet au connecteur de saisir le fil Diam tre de fil 1 5 0 5 mm2 16 20 AWG Le connecteur 5 broches peut accepter des diam tres de fil de 1 5 0 5 mm2 16 20 AWG Longueur du c ble d nud 8 9 mm 0 3 0...

Page 10: ...re for further RF testing If a sample is requested the required performance testing may take up to 3 weeks starting from when the sample is received by Lutron For best RF performance of the LL INTMOUN...

Page 11: ...25 5 mm 1 po du LL INTMOUNT Le LL INTMOUNT n est pas tanche et ne doit pas tre mont dans un endroit o il sera en contact direct avec de l eau Toutefois il poss de un rev tement enrobant et peut r sist...

Page 12: ...cher correctement le joint interne 3 Inspectez visuellement pour v rifier que la lentille du PIR en plastique est correctement install e et n est pas inclin e par rapport au luminaire Une inclinaison...

Page 13: ...de mise sous tension du luminaire Lorsque le LL INTMOUNT s allume il fait passer le luminaire par diff rents tats pour permettre au fabricant de d terminer si le luminaire a t c bl correctement La s q...

Page 14: ...ue du Nord et du Sud tats Unis Canada Cara bes 1 800 523 9466 Mexique 1 888 235 2910 Am rique Centrale du Sud 1 610 282 6701 SI GE EUROP EN Royaume Uni Lutron EA Ltd 6 Sovereign Close London E1W 3JF R...

Reviews: