CDD3000-HF Operation Manual
3-15
3 Installation
DE
EN
FR
IT
ES
FR
Mains filters
Note:
Compliance with the limit curves to attenuate the line-borne
interference voltage and the interference emitted from the
CDD3000-HF drive controller depends on
· use of a line choke (recommended),
· the length of the motor cable and
· the pre-set clock frequency (4, 8, 12 or 16 kHz) of the
CDD3000-HF drive controller power stage. For further
information please contact your project engineer.
Wire cross-section
.
1)
The minimum cross-section of the mains power cable is based on the local
provisions (VDE 0100 Part 523, VDE 0298 Part 4), the ambient temperature
and the specified rated current of the CDD3000-HF drive controller.
Size
Power range
Mains filter
BG1 ... 4
1.0 ... 11.8 kVA
Internal
1) For supplementary components see CDD3000-HF Order Catalogue
drive controller for
highspeed drives
Connection
load
[kVA]
Max. possible wire
cross-section of
terminals [mm²]
Recommended mains
fusing (gL)
[A]
CDD32.003-HF
CDD32.004-HF
1.0
1.7
2.5
1 x 10
1 x 10
CDD32.006-HF
CDD32.008-HF
CDD34.003-HF
CDD34.005-HF
2.3
3.0
1.6
3.0
2.5
1 x 16
1 x 16
3 x 10
3 x 10
CDD34.006-HF
4.2
2.5
3 x 10
CDD34.008-HF
CDD34.010-HF
5.7
7.3
2.5
3 x 10
3 x 16
CDD34.014-HF
CDD34.017-HF
10.2
12.4
4.0
3 x 20
3 x 25
CDD34.024-HF
CDD34.032-HF
17.5
23.3
10
3 x 35
3 x 50
Table 3.8
Wire cross-sections and mains fuses (conformance to VDE
0298 is required)
1