4-12
Issue 1.0
March 2001
365-575-389
Installation Manual
Power Cable Installation
Miscellaneously Mounted OLS
Shelves
Introduction
This section describes the installation of the A and B power cables for the
Miscellaneously Mounted OLS Shelves.
Each feeder capacity in the miscellaneous mount shelf must be 15 amperes
(unless otherwise specified by the customer) at the BDFB.
For power cable installation information of multiple OLS shelves in a single bay,
OLS shelf with OT shelves in the same bay, single OLS or OT shelves, or multiple
OT shelves in the same bay, refer to the appropriate section of this chapter.
Available Power
Cables
Table 4-3 lists power cables available for installing a miscellaneous OLS shelf.
Table 4-3.
Available Power Cables
Power Cable
Installation
For the Miscellaneous Mounted OLS Shelf, the power cables are a single feed.
Each miscellaneous shelf is powered individually. Install as follows:
(Continued on next page)
ED-9C103-22
Cable Group
Bay Type
Cable Length
(ft.)
Use With
Power Bus
Color
3
Miscellaneous Mount
15
A
Red
4
Miscellaneous Mount
15
B
Blue
13
Miscellaneous Mount
As Required
A
Red
14
Miscellaneous Mount
As Required
B
Blue
Step
Action
1
Turn the power breakers off, or do not install fuses, at the BDFB.
2
Verify the circuit packs are not installed in the shelves.
Leave the fuses out or breakers off until performing the steps in
Chapter
7, Powering
, of this manual.
Summary of Contents for WaveStar OLS 40G
Page 4: ......
Page 12: ...Contents xii Issue 1 0 March 2001 365 575 389 Installation Manual...
Page 24: ...Tables xxiv Issue 1 0 March 2001 365 575 389 Installation Manual...
Page 126: ...3 50 Issue 1 0 March 2001 365 575 389 Installation Manual Equipment Installation...
Page 156: ...4 30 Issue 1 0 March 2001 365 575 389 Installation Manual Power Cable Installation...
Page 228: ...5 72 Issue 1 0 March 2001 365 575 389 Installation Manual Wired Cable Installation...
Page 366: ...7 16 Issue 1 0 March 2001 365 575 389 Installation Manual Powering...
Page 436: ...9 46 Issue 1 0 March 2001 365 575 389 Installation Manual Local Installation Testing...
Page 487: ...Issue 1 0 March 2001 12 15 12 Troubleshooting 12 Contents Background 2 Troubleshooting Table 3...
Page 500: ...12 28 Issue 1 0 March 2001 365 575 389 Installation Manual Troubleshooting...
Page 501: ...Issue 1 0 March 2001 A 1 A Releases 1 0 and2 0LBO Selection Tables A Contents Overview 2...
Page 571: ...Issue 1 0 March 2001 H 1 H Optical Protection Switch OPS H Contents Overview 2...