unexpected CP type
....................................................................................................................................................................................................................................
unexpected CP type
This alarm indicates that a different but supported circuit pack is
inserted in a slot that is already provisioned for another type of circuit
pack.
Alarm Data
Value/Meaning
Reported Alarm
Level(s)
Critical (CR), Minor (MN)
Not Alarmed if the network element is in the
provisioned Ring Upgrade Mode
AID (type)
Slot
Date
month/day/year that condition was detected
Time
hour:minute:second that condition was detected
Probable Cause
FACTERM
Effect on
Service
CR = SA
MN = NSA
Not Alarmed = Standing Condition (SC)
Alarm Entity
Type
EQPT
Description
unexpected CP type
Likely Cause
The wrong circuit pack was inserted into an
unprotected slot. - CR (SA).
The wrong circuit pack was inserted into a
protected slot - MN (NSA).
An unexpected compatible circuit pack is in a slot
as part of a node or network upgrade - Not
Alarmed (NSA).
Visible
indication
Lighted
CR/MJ
or
MN/ABN
LED on SYSCTL
faceplate and a continuously lighted
FAULT
LED
on the affected circuit pack.
Action
If a node or network upgrade is in progress, no
action is necessary. The Standing Condition will
clear when the upgrade is complete.
Otherwise, proceed to
Alarms, conditions, and error messages
....................................................................................................................................................................................................................................
3 - 9 0
Lucent Technologies
365-372-333 R2.1