Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
Issue 8 July 1999
Installation 5 - 7
Installation Tools
The following tools are required for installing rectifiers.
•
Material handling equipment to unload rectifiers at site,
remove them from shipping containers, and place them in
final positions
•
Common electrician’s hand tools, including jeweler’s
screwdriver, electrical tape, wire cutters and strippers, 10
AWG to 1/0 AWG wire
•
Proper crimping tools and dies for connectors used
•
Common mechanic’s hand tools, including flat blade
screwdriver (.30 inch blade width), socket and torque
wrench for 3/8 inch bolts, channel lock pliers for ac conduit
tightening, hammer, and crowbar for uncrating
•
5/16” hex Allen wrench for dc output connection at CBA1
•
Three 3/8-16 lifting eyebolts
•
Digital Multimeter (DMM) Fluke
®
8060A or equivalent
with ±0.02 percent accuracy on dc scale
Figure 5-3: Typical J85502C-1 125-ampere Rectifier
With Door Open and Diode Heat Sink Removed
CM2 control
board (205A1)
CM6 ac/dc voltage
monitor board
mounted on connector
JA1 of CM2
Label showing
major components,
ac field wiring, and
torque values
K1 contactor
mounted on
back wall
Bus bar assembly
Output volts
adjustment
potentiometer
CBA1 circuit
breaker
CM3 digital
meter board
(207A)
CM1 option
board
(ED-83158-30)