Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
Issue 8 July 1999
Product Description 2 - 9
•
The EQUAL ADJ potentiometer provides for manual
adjustment of the equalize voltage.
•
The EQUALIZE LED indicates that the equalize mode is
in use.
•
The OUTPUT VOLTS ADJ potentiometer provides for
manual adjustment of the output float voltage.
•
The REG test jacks allow for measuring the plant output
voltage at the points where the remote sense leads are
connected. This measurement is accurate only when the
remote sense leads are connected.
•
The 1/2 Amp +V and -V alarm fuses protect the voltage
sense leads to the rectifier control and regulation circuits.
These fuses are attached to the control panel inside the
rectifier door.
•
The DC OUTPUT circuit breaker protects the plant from
rectifier malfunction and excessive current, and may be
used to disconnect the rectifier from the battery. An output
Figure 2-1: Control Panel on the J85502C-1