Technical data for PDP
....................................................................................................................................................................................................................................
Specifications
The PDP has the following specifications:
Item
Quantity / Size
Power consumption,
Circuit breakers
Release 1.0 and 2.0:
•
max. 2700 W
•
68 A circuit breakers must be used in the External Battery
and Fuse Bay (BDFB)
•
63 A circuit breakers are part of the subracks.
Release 2.1:
•
max. 3500 W
•
Circuit breakers
≥
100 A must be used in the External
Battery and Fuse Bay (BDFB)
•
100 A circuit breakers are part of the subracks.
Voltage range
(all components)
-48 to -60 V battery voltages
(-40.5 V minimum, -72 V maximum)
Power feeds
3 power feeders (only 2 are necessary for one rack)
Ground
3 ground-connection points (only 2 are necessary for one rack)
Dimensions (H x W x D)
70 mm [2.756”] x 482.6 mm [19”] x 60 mm [2.362”]
Figure 3-4 Layout
ETSI-2 installation
Mechanical installation
....................................................................................................................................................................................................................................
3 - 1 8
Lucent Technologies
365-374-074
Issue a, April 2002