4 - 16 Installation and Setup
Issue 4 August 1998
Optional
Rectifier Adapter
Board (RAB)
The Rectifier Adapter Board (RAB) may be added to the
controller to extend the features described in this manual to
pre-Lineage
®
rectifiers either manufactured by Lucent
Technologies or manufactured for Lucent Technologies to a J or
KS specification. (See Figure 4-11.) DIP switches S1 through S6
on the RAB must be set corresponding to the port used for each
non-Lineage
®
rectifier connected to the controller. (See Figure
4-12.) Table 4-D lists the cables required for the various
rectifiers. Those rectifiers not listed will require a termination
either to a screw or wire wrap terminal at the rectifier end. See
Table 4-E and Figure 4-10.
The RAB also permits non-Lucent Technologies rectifiers to be
used with the controller. DIP switches S1 through S6 on the
RAB must be set corresponding to the port used for each of the
non-Lineage
®
rectifiers connected to the controller. For
rectifiers not manufactured by Lucent Technologies, the cable
will always require field termination to a wire wrap or screw
terminal. See “Mixed Types of Rectifiers in One Plant” in
Section 2.
A rectifier must have a feature in order for the ECS-6U to extend
that feature to the system. For example, if a rectifier is not
capable of acting upon an automatic restart signal, the rectifier
will not restart even though the controller sends the signal to the
rectifier.
The RAB is required for all Lucent Technologies non-Lineage
®
2000 rectifiers and all rectifiers not manufactured by Lucent
Technologies.
Figure 4-12: RAB DIP Switch Settings
EAT2 DIP SWITCH SETTINGS - S1 THRU S6
RECTIFIER OPTIONS
(NON-LUCENT RECTIFIERS ONLY)
SWITCH POSITION
*
*
*
*
*
*
1 THRU 8
ON
OFF
-
-
-
-
9
-
-
ON
OFF
OFF
ON
10
-
-
OFF
ON
ON
OFF
24V
48V
ALARM = OPEN
ALARM = CLOSURE
ALARM NOT PROVIDED
NO RECTIFIER
VOLTAGE
MAN
ALARM
ALL SWITCHES MUST BE SET
ACCORDING TO THIS TABLE.
SETTINGS TO BE USED WHEN
NO RECTIFIER OR A LUCENT
RECTIFIER IS CONNECTED TO
THE CORRESPONDING PORT.
-
-
NOTE:
OFF=OPEN
ON=CLOSED