Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
Issue 6 May 1999
Engineering, Planning and Ordering 3 - 19
Order pre-engineered battery cable kits for use with VR batteries
in supplemental bays can be ordered with the ECS battery plant.
These kits have been engineered for the typical ECS
configurations presented in the J85500G-2 drawing. The kits
contain the following items:
•
Appropriate length and gauge of KS20921 wire
•
Appropriate lugs for termination at the battery and at the dc
distribution
•
Crimping information
•
Heat shrink tubing
For nontypical ECS configurations where the supplementary
bays are not located adjacent to the initial bay, battery cables
must be engineered to fit the individual installation.
A wide range of circuit breakers and fuses is available for dc
distribution overcurrent protection. The ratings of these circuit
breakers are from 5-600 amperes and the ratings of thge fuses are
from 1-200 amperes. The breaker or fuse rating for a given circuit
is selected by the criteria covered above under Overcurrent
Protection.
Table 3-E: Single Hole Terminal Lugs
KS-5482
Wire
KS-20921
Wire
WP-91412
List
Comcode
Bolt Size
Die
10
10
93
406338145
10
R5473-5
8
8
1
405347402
10
Red
8
8
74
405356189
0.250
Red
6
6
2
405347436
0.250
Blue
4
4
4
405347543
0.250
Grey
2
-
53
405348186
0.250
Brown
-
2
7
405347659
0.250
Green
1/0
-
55
405348210
0.375
Pink
-
1/0
10
405477717
0.375
Black
2/0
-
10
405477717
0.375
Black
-
2/0
17
405347790
0.375
Orange
4/0
-
58
405348244
0.375
Purple
-
4/0
78
406021741
0.375
Yellow