Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
2 - 10 Product Description
Issue 6 May 1999
Termination points: Termination information for load leads for
each distribution panel is listed in Table 2-C.
All the load lead termination points can be accessed from the
front by removing the associated blank panel located above or
below each fuse panel. The corresponding return for each load
lead is terminated to the Plant Discharge RTN Bus.
Table 2-B: ECS/GPS Battery Plant Breaker and Fuse Panels
List
Number
Distribution
Type
Maximum Number
of Fuses/Breakers
Size (Amps)
Ordering
Information
20
30
31
32
33
34
35
36
Breaker*
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
17 or 21
1 to 4
24
8
4
2
3
2
19
5-100
125-600
1-30
1-60
70-100
110-200
70-200
70-600
3-60
Table 2-D
Table 2-E
Tab;e 2-F
Table 2-G
Table 2-H
Table 2-J
Table 2-K
Table 2-L
*An optional capacitor charge feature/panel is available with List 20 and occupies 4
slots on the breaker panel.
Table 2-C: Load Lead Termination Points
J85500G-2
List
*Maximum Wire Size
**Output Terminal Information
# of Holes
Hardware
20
30
31
32
33
34
35
36
1 or 2 pole: 4/0
3 pole: 350 MCM
8
4
4/0
4/0
4/0
4/0
4/0
1
1
1
1
1
1
1
1
.375-16
10-32
.250-20
.375-16
.375-16
.375-16
.375-16
.375-16
* For larger gauge, install parallel connectors (KS-21500 or equal) outside bay.
** For corresponding Terminal Lugs, refer to Table 3-D and 3-E.