Lucent Technologies ECS Minicell Battery Plant H569-420
6 - 2 Installation Tables
Issue 5 February 1997
Table 6-B: Controller Factory Default Settings
Jumper Settings
Board
Header
Jumper
Pins
Function
Backplane
846575280
P602.1
1 & 2
+24 Volts
P602.2
1 & 2
P602.3
1 & 2
P602.4
1 & 2
CP1
P105
1 & 2
Restart Enabled
P106
1 & 2
Equalize Disabled
P108
1 & 2
For SR Series Rectifiers
CP4
(113B)
Display
P401
or
SW409
1 & 2
Shunt size less than 1000 amperes
CP3
P302
1 & 2
+24 Volts
Switch Settings
Board
Switch
Functio
n
Switch Settings
-1
-2
-3
-
-4
-5
-6
-7
-8
CP1
SW101
HV/EQ
+29.25
V
0
1
1
0
1
1
N/
A
N/
A
SW102
HV/FL
29.25V
0
1
1
0
1
1
N/
A
N/
A
SW103
BD
+26.50
V
0
0
0
1
1
1
N/
a
N/
A
SW109
Meter
Shunt
600
amps
1
0
0
0
0
0
N/
A
N/
A
CP2
SW202
See
Table
6-3
0
0
0
1
1
1
0
0