Lucent Technologies Galaxy Power System 4804AP H569-450
Issue 1 June 2000
Troubleshooting Millennium Systems 14 - 13
RECT Alarm LED
Table 14-E: Rectifier Related Alarms
(See Figures 13-6 and 13-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller
Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)
RECT
MAJ
ID Not
Configured
None
None
Rectifier ID
number has not
been set.
1. Press ON/STBY
switch up and
hold for five
seconds until
display starts
blinking “0”.
2. Release switch;
display should
continue to blink.
3. Depress switch
and release.
Display will
increment up one
number on each
release of the
switch, but will
remain flashing.
4. Once the desired
ID number
appears, depress
and hold the
switch for five
seconds. The
display will cease
to blink, and then
revert to the
rectifier current.
RECT
MAJ
ID Conflict
None
None
Two or more
Rectifiers have
the same ID
number.
See above.
RECT
MAJ
Multiple
Rectifier
Fail
ALM
None
More than
one rectifier
has an ALM
LED lit.
See alarms listed
below.