![Lucent Technologies 2VR250E Product Manual Download Page 55](http://html1.mh-extra.com/html/lucent-technologies/2vr250e/2vr250e_product-manual_1946081055.webp)
Lucent Technologies Enhanced VR Series Batteries
Issue 5 December 1998
Discharge and Power Data 9 - 1
9
Discharge and Power Data
Constant
Current
Discharge Data
Tables 9-A to 9-C and Figures 9-1 to 9-8 display constant current
discharge data at 25°C (77°F) for Lucent Technologies
Enhanced VR batteries. The numbers in the tables represent the
discharge current for a particular reserve time to the
corresponding end cell voltage. The capacity in ampere-hours is
obtained by multiplying the discharge current by the reserve
time.
The data in these tables were derived from discharge data that
were temperature corrected assuming a temperature correction
factor of 0.25% per degree Fahrenheit. For temperatures above
77°F, adjust the discharge times by adding 0.25% per degree
Fahrenheit. For temperatures below 77°F, adjust the discharge
times by subtracting 0.25% per degree Fahrenheit.
The data in these tables represent a minimum of 100% capacity
between the first and last terminals of the battery string and do
not include any connections between the battery and the load.