Page 4
Tech Help Line
UK -
0845 194 7584
Non UK -
+44 (0)1952 238 100
Visit our website at
Luceco is a registered trade mark of Nexus Industries Ltd.
Supplied by
BG Electrical Ltd
Stafford Park 1 TF3 3BD ENGLAND
www.luceco.co
Installation & Operating Instructions
EMERGENCY LIGHTING TESTING
Months 1 to 11 inclusive – Function Test, interrupt the permanent/UnSwitched supply and check the luminaire operates in Emergency
mode at reduced output
Month 12 (Annual) – As months 1 to 11 but for a full 3 hour duration
Luminaire Ref / Location:
........................................
In Case of difficulty, contact the Installation Engineers:-
Tel: .........................................................
LBM290X11E40
Duration 3 Hours
Lamp Type - LED
INITIAL USE AND ROUTINE TESTING
From initial install the downlight will require up to 24 hours for the batteries to be fully charged and provide the rated 3HR duration in
Emergency mode. Then following subsequent Emergency use, from full discharge will take approx. 14hrs to fully recharge batteries.
It is important that the luminaire is routinely tested to ensure the batteries are conditioned and also to fully comply with BS5266.
A function test should be conducted every month with an annual test of the full 3hr duration. Records can be kept on the adjacent table.
It is recommended that batteries are replaced every 4 years to ensure the optimum charging cycle is maintained.
Month
Test
1
Function
2
Function
3
Function
4
Function
5
Function
6
Function
7
Function
8
Function
9
Function
10
Function
11
Function
Annual
Full Test
Signed
Date
Fifth Year
Signed
Date
Fourth Year
Signed
Date
Third Year
Signed
Date
Second Year
Signed
Date
First Year
WARRANTY
Products are protected by warranty for a period of 3 year warranty from date of purchase against defects in material and workmanship
(unless otherwise stated). Should a product fail to perform as described within the warranty period it will be repaired or replaced with
the same or equivalent product by Luceco, free of charge provided that you: (1) return the product to us with shipping charge prepaid,
(2) provide us with proof of the original date of purchase and (3) quote our return authorization number
Repaired or replaced products will be returned to you with shipping charges prepaid. Replacement products may be refurbished
or contain refurbished materials. If in our sole discretion, we are unable to repair or replace a defective product, we will refund the
purchase price of the product
This warranty will not apply if in our judgment, the product fails due to damage in shipment, handling, storage, accident, abuse or
misuse, or if it has been used in a manner not conforming to our product instructions, has been modified in any way, or has any serial
number removed or defaced. Repair or attempted repair will void this warranty. Our maximum liability under the terms of this warranty
is limited to the purchase price of the product covered by the warranty
The warranty is given under English Law. If any part of this warranty is deemed unenforceable (including any provision in which we
exclude our liability to you) the enforceability of any other parts of the warranty will not be affected. These terms do not reduce your
statutory rights
THESE TERMS AND CONDITIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
For further details, terms and conditions and online registration please see
www.luceco.co
SUGGESTED METHOD OF INSTALLATION
The bulkhead is designed for mounting in any of the
following options: –
• Surface Wall Mounting
• Surface Ceiling Mounting
1. Surface mounted options may use rear cable entry for flush
mounting or there is facility for surface Conduit ‘besa’ box
mounting or side conduit entry. (Image 1)
2. With the method of mounting chosen, remove the front
Diffuser, by undoing the three front Screws. (Image 2)
3. To remove LED tray, loosen two retaining screws,
and twist tray clockwise and remove. (Image 3)
4. This Bulkhead can be mounted on ceilings and vertical walls.
Ensure the mounting surface is suitable for installation.
Once mounting points are decided, drill out mounting holes
and any cable entry points needed.
5. Cable Entry Points must be drilled out with a 20mm bit,
cleaned of any loose burrs and fitted with a suitable
IP65 gland, if the IP65 rating is to be maintained.
Otherwise the IP rating would be reduced.
Tech Help Line
UK -
0845 194 7584
Non UK -
+44 (0)1952 238 100
Visit our website at
Luceco is a registered trade mark of Nexus Industries Ltd.
Supplied by
BG Electrical Ltd
Stafford Park 1 TF3 3BD ENGLAND
www.luceco.co
LED
IP65
Mosi Emergency Bulkhead
PART CODE: LBM290W11E40, LBM290B11E40
Installation & Operating Instructions
SPECIFICATIONS
•
Suitable for use with Mains voltage of 220-240V AC
•
This product must be disconnected before insulation
resistance testing of the lighting circuit
•
Check for electrical cables and pipes before installation
NOTE
– To comply with regulations, installation must be carried
out by qualified electrician and in accordance with the current IEE
Wiring Regulations (BS7671) and Building Regulations.
ENSURE ELECTRICAL SUPPLY IS DISCONNECTED/ISOLATED
BEFORE COMMENCING INSTALLATION
•
To maintain the IP65 rating of the bulkhead, a suitable 20mm
cable gland should be used in conjunction with rubber
insulated cable to ensure the supply cable is sealed in the
gland. Failure to use a gland and/or rubber insulated cable
may result in water ingress
Page 1
4
1
cable entry
points
cable entry
points
2
loosen
screws here
3
loosen
screws here
3HR
EMERGENCY
CRI
80
>
IP65
RATED
3
GUARANTEE
year