LST Vds BC216-1 Brochure & Specs Download Page 1

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

BC216-1_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

•   For application in small and 

mid-sized systems

•   Analogue ringbus technology with 

unshielded detector cabling

•  Addressable conventional technology
•  Menu-driven operation
•   Easy commissioning through 

AUTO setup

•  32–bit multiprocessor system
•  EN 54/VdS-certifi ed

Fire is a permanent threat to life and property. There-

fore, immediate response to a fi re is imperative. The 

main objective of the fi re detection control panel Series 

BC216  is  to  alarm  and  to  react  in  time  and,  conse-

quently, save lives and protect property. For decades 

LST have focused their aims to undertaking unrivaled 

efforts in order to realize new innovations in the security 

area. Research, development and production are loca-

ted within LST premises, thus guaranteeing fl exible and 

reliable individual solutions.

Using a 32-bit multiprocessor system, the fi re detection 

control panel Series BC216 ensures topmost effi ciency 

and speed – prerequisites for saving lives and minimi-

zing damage to property.

The fi re detection control panel BC216-1 is designed as 

a modular system. According to your system‘s concept 

and size, it can be expanded individually.

The control panel provides two slots for the connection 

of  function  modules  (Conventional  Detector  Interface 

GIF8-1 or Loop Interface LIF64-1) to which a maximum 

of 16 detector lines in addressable conventional techno-

logy or a maximum of two ADM loops or a combination 

of the both can be connected. In this way, you obtain 

the highest degree of fl exibility for virtually any task.

The ADM loop principle offers intelligent analogue ring-

bus  technology  with  bi-directional  data  transfer.  Each 

loop provides for the software-aided administration of 

up to 198 physical address points in a maximum of 128 

detector  zones.  Addressable  conventional  technology 

allows  for  the  connection  of  automatic  and  non-auto-

matic fi re detectors as well as the unambiguous iden-

tifi cation  of  the  activated  detector  in  the  event  of  an 

alarm.

Depending on the respective system, a Fire Brigade In-

terface FWI2-1, a Fire Brigade Interface Additional Board 

FWZ2-1, an LED-Display Field LAB48 as well as further 

optional componentries can be installed in addition.

Easy  parameterisation  on  the  control  panel‘s  display 

and operating unit, via a PC keyboard, or by means of 

a PC software enables you to tailor the control panel to 

your individual requirements.