![LST ÜMM-55000-833 Specification Sheet Download Page 1](http://html1.mh-extra.com/html/lst/umm-55000-833/umm-55000-833_specification-sheet_1944699001.webp)
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
UMM-55000-833_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The addressable Monitor Module ÜMM-55000-833
serves for the line-monitored integration of contact de-
tectors, such as manual call points, sprinkler system
contacts or supervising contacts, into the bidirectional
communication on the ADM loop with Apollo/Discovery
protocol. The address is easily selected by means of an
integrated DIL switch, which is accessible through an
opening in the case. The module provides 6 wires for
establishing the desired connections. An optional remo-
te indicator can be connected to the module.
• ADM loop technology with
Apollo/Discovery protocol
• One line-monitored input
• Integration of contact detectors into
the ADM loop
• Output for optional remote indicator
• Setting of module address by means
of address switch
• Small design
Specifi cations
Operating voltage
Supply through loop voltage
Current consumption
1mA (quiescent)
Ambient temperature
-20°C to +70°C
Dimensions L × W × H
76 × 47 × 14 (mm)
Colour
white
Weight
46g
Order number
249061
Order name
Monitor Module/Anal./XP95/Apo ÜMM-55000-833